S.C. Code Regs. § 61-79.264.O.347

Current through Register Vol. 48, No. 3, March 22, 2024
Section 61-79.264.O.347 - Monitoring and inspections
(a) The owner or operator must conduct, as a minimum, the following monitoring while incinerating hazardous waste:
(1) Combustion temperature, waste feed rate, and the indicator of combustion gas velocity specified in the facility permit under these regulations must be monitored on a continuous basis. (amended 11/90)
(2) CO must be monitored on a continuous basis at a point in the incinerator downstream of the combustion zone and prior to release to the atmosphere.
(3) Upon request by the Department, sampling and analysis of the waste and exhaust emissions must be conducted to verify that the operating requirements established in his permit application achieve the performance standards of Section264.343.
(b) The incinerator and associated equipment (pumps, valves, conveyors, pipes, etc.) must be subjected to thorough visual inspection, at least daily, for leaks, spills, fugitive emissions, and signs of tampering.
(c) The emergency waste feed cutoff system and associated alarms must be tested at least weekly to verify operability, unless the applicant demonstrates to the Department that weekly inspections will unduly restrict or upset operations and that less frequent inspection will be adequate. At a minimum, operational testing must be conducted at least monthly.
(d) This monitoring and inspection data must be recorded and the records must be placed in the operating record required by 264.73 of this regulation and maintained in the operating record for five years.

S.C. Code Regs. 61-79.264.O.347

Amended by State Register Volume 14, Issue No. 11, eff November 23, 1990; State Register Volume 16, Issue No. 12, eff December 25, 1992; State Register Volume 32, Issue No. 6, eff June 27, 2008.