S.C. Code Regs. § § 61-78.2700.2704

Current through Register Vol. 48, No. 10, October 25, 2024
Section 61-78.2700.2704 - Receptacles (II)
A. Each patient room shall have duplex grounding type receptacles, to include one (1) at the head of each bed in accordance with the applicable code in Section 2102.
B. Each patient bed location shall have a minimum of two (2) duplex receptacles.
C. Each patient bed location shall be supplied by at least two (2) branch circuits.
D. Duplex receptacles for general use shall be installed approximately fifty (50) feet apart in all corridors and within twenty-five (25) feet of the ends of corridors.

S.C. Code Regs. § 61-78.2700.2704

Replaced and amended by State Register Volume 40, Issue No. 04, eff. 4/22/2016.