Section 61-75.2500 - HEATING, VENTILATION, AND AIR CONDITIONING
A. The Facility shall maintain documentation of Annual heating, ventilation, and air conditioning system inspections by a certified or licensed technician. (I)
B. The Facility shall maintain a temperature of between seventy-two (72) and seventy-eight (78) degrees Fahrenheit in Participant areas. (II)
C. The Facility shall not install a heating, ventilation, and air conditioning supply or return grille within three (3) feet of a smoke detector.(I)
D. The Facility shall not install heating, ventilation, and air conditioning grilles in floors. (II)
E. The Facility shall filter and maintain intake air ducts that prevent the entrance of dust, dirt, and other contaminating materials. The Facility shall ensure the system does not discharge in such a manner that would be an irritant to the Participants, Staff, or Volunteers. (II)
F. The Facility shall have either operable windows or approved mechanical ventilation in the bathrooms. (II)