Current through Register Vol. 48, No. 10, October 25, 2024
Section 61-58.4.C - Finished Water Storage(1) General-- (a) Sizing--Where fire flows are provided, tanks shall be sized to provide two (2) hours of supply for a combined flow of peak hour domestic plus fire flow; or, the storage capacity (or equivalent capacity) shall equal one half ( 1/2) the maximum daily consumption, whichever is greater. Either requirement may be reduced when the source and treatment facilities have sufficient capacity with auxiliary power to supplement peak demands of the system.(b) Isolation of Tank--Storage structures shall be designed so they can be isolated from the distribution system for the purpose of draining, maintenance and repair. A sample tap shall be provided on the tank or on the tank side of the isolation valve.(c) Level controls--Adequate controls shall be provided to automatically maintain levels in distribution system storage structures. Where telemetry is not provided for water level measurement, a float type level gauge and visible target shall be provided. Altitude valves or equivalent controls may be required for a second and subsequent structures on the system.(d) All tanks shall be readily accessible at all times for inspection and maintenance.(2) Atmospheric Ground Storage, Elevated Tanks, and Standpipes. (a) General--The materials and designs used for finished water storage structures shall provide stability and protection of the stored water. Steel structures shall be designed in accordance with current American Waterworks Association (AWWA) Standard D-100 concerning steel tanks, standpipes, reservoirs, and elevated tanks whenever they are applicable. Other materials of construction are acceptable when properly designed to meet the requirements of this Section.(b) Location of ground-level reservoirs (i) The bottom of reservoirs and standpipes shall be above the one hundred (100) year flood level.(ii) When the bottom must be below normal ground surface, it shall be placed above the ground water table. Sewers, drains, standing water, and similar sources of possible contamination must be kept at least fifty (50) feet from the reservoir. Water main pipe, pressure tested in place to fifty (50) pounds per square inch without leakage, may be used for gravity sewers at distances greater than twenty (20) feet and less than fifty (50) feet.(iii) The top of a reservoir shall not be less than two (2) feet above normal ground surface. Clearwells constructed under filters may be exempted from this requirement when the total design gives the same protection.(c) Sanitary Protection--All finished ground level or elevated water storage structures shall have suitable watertight roofs which exclude birds, animals, insects, and excessive dust.(d) Protection from trespassers--Fencing, locks on access manholes, and other necessary precautions shall be provided to prevent trespassing, vandalism, and sabotage.(e) Drains--Adequately sized drains shall be provided. No drain on a water storage structure may have a direct connection to a sewer or storm drain. A flap valve or other means of covering the open outlet of the drain shall be provided.(f) Overflow--The overflow pipe shall be of sufficient diameter to permit the discharge of water equal to or greater than the filling rate; but shall not be less than four (4) inches in diameter. All atmospheric storage structures shall be provided with an overflow which is brought down to an elevation between twelve (12) and twenty-four (24) inches above the ground surface, and discharges over a drainage inlet structure or a splash pad. A flap valve or number four (4) mesh non-corrodible screen shall be provided on the outlet. No overflow may be connected directly to a sewer or storm drain. All overflow pipes shall be located so that any discharge is visible.(g) Access--Finished water storage structures shall be designed with reasonably convenient access to the interior for cleaning and maintenance. Manholes above the water-line shall: (i) be framed at least four (4) inches above the surface of the roof at the opening on ground-level structures;(ii) be fitted with a solid watertight cover which overlaps the framed opening and extends down around the frame at least two (2) inches; and,(iii) have a locking device.(h) Vents--Finished water atmospheric storage structures shall be vented. Overflows shall not be considered as vents. Open construction between the sidewall and roof is not permissible. Twenty-four (24) mesh non-corrodible screens, or equivalent, shall be used on all vents. Vents shall be constructed to: (i) prevent the entrance of surface water and rainwater;(ii) exclude birds and animals;(iii) exclude insects and dust, as much as this function can be made compatible with effective venting.(iv) "The vent shall be constructed to prevent imploding of the tank during a rapid discharge of water from the tank."(i) Roof and sidewall--The roof and sidewalls of all structures must be watertight with no openings except properly constructed vents, manholes, overflows, risers, drains, pump mountings, control ports, or piping for inflow and outflow. (i) Any pipes running through the roof or sidewall of a finished water storage structure must be welded, or properly gasketed in metal tanks. In concrete tanks, these pipes shall be connected to standard wall castings which were poured in place during the forming of the concrete. These wall castings should have seepage rings imbedded in the concrete.(ii) Openings in a storage structure roof or top, designed to accommodate control apparatus or pump columns, shall be curbed and sleeved with proper additional shielding to prevent the access of surface or floor drainage water into the structure.(iii) Valves and controls shall be located outside the storage structure so that the valve stems and similar projections will not pass through the roof or top of the reservoir.(j) Drainage of roof--The roof of the storage structure shall be well drained. Downspout pipes shall not enter or pass through the reservoir. Parapets, or similar construction which would tend to hold water and snow on the roof, will not be approved unless adequate waterproofing and drainage are provided.(k) Safety--The safety of employees must be considered in the design of the storage structure. (i) Ladders, ladder guards, balcony railings, and safely located entrance hatches shall be provided where applicable.(ii) A platform at the top of the ladder to provide a place for the climber to stand on while unhooking the safety harness shall be provided.(iii) Elevated tanks with riser pipes over eight (8) inches in diameter shall have protective bars over the riser opening inside the tank.(l) Freezing--All finished water storage structures and their appurtenances, especially the riser pipes, overflows, and vents, shall be designed to prevent freezing which will interfere with proper functioning.(m) Internal catwalk--Every catwalk over finished water in a storage structure shall have a solid floor with raised edges so designed that shoe scrapings and dirt will not fall into the water.(n) Silt stop--The discharge pipes from all reservoirs shall be located in a manner that will prevent the flow of sediment into the distribution system. Removable silt stops should be provided where feasible.(o) Grading--The area surrounding a ground-level structure shall be graded in a manner that will prevent surface water from standing within a fifty (50) foot radius.(p) Painting and/or cathodic protection--Proper protection shall be given to metal surfaces by paints or other protective coatings, by cathodic protective devices, or by both. All paint coatings which come into contact with drinking water shall be certified as meeting the specifications of the American National Standard Institute/National Sanitation Foundation Standard 61, Drinking Water System Components--Health Effects. The certifying party shall be accredited by the American National Standards Institute. Hot applied wax, cold applied wax, grease, and coal tar coatings are not acceptable.(q) Disinfection--Finished water storage structures shall be disinfected in accordance with current American Waterworks Association (AWWA) Standard for the disinfection of water storage facilities. Prior to sampling, the chlorine residual must be reduced to normal system residual levels or be non-detectable in those systems not chlorinating. A minimum of two (2) samples must be collected and analyzed for total coliform bacteria. These samples must be collected at least twenty-four (24) hours apart and the results must show the absence of total coliform bacteria. The chlorine residual must also be measured and reported. If the membrane filter method of analysis is used for the coliform analysis, non-coliform growth must also be reported. If the non-coliform growth is greater than eighty (80) colonies per one hundred (100) ml, the sample result is invalid and must be repeated. All samples must be analyzed by a certified laboratory. The Department may request that heterotrophic plate count analyses be conducted on a case-by-case basis where disinfection problems are suspected.(3) Washwater Tanks--Washwater tanks shall be designed in accordance with R.61-58.4(C)(1)(C)(1) and shall be sized, in conjunction with available pump units and finished water storage, to provide the backwash water required by R.61-58.3(D)(5)(a)(xi)(D)(5)(a)(xi). Consideration must be given to the backwashing of several filters in rapid succession.(4) Clearwell-- (a) Clearwell storage shall be sized, in conjunction with distribution system storage, to relieve the filters from having to follow fluctuations in water use.(b) When finished water storage is used to provide the contact time for chlorine, special attention shall be given to size and baffling.(c) An overflow shall be provided.(d) Finished water must not be stored or conveyed in a compartment adjacent to unsafe water when the two compartments are separated by a single wall.(5) Hydropneumatic (Pressure) tanks--Hydropneumatic (pressure) tanks, when provided as the only storage facility, are acceptable only in small water systems. For systems serving more than three hundred (300) taps or more than one thousand (1000) people, elevated storage shall be provided. Pressure tank storage shall not to be considered for fire protection purposes, unless standby power is provided and the pumping capacity from wells or ground storage exceeds the fire flow demand with the largest well or pump out of service. Pressure tanks five hundred (500) gallons and larger shall meet the requirements of the American Society of Mechanical Engineers for the construction and installation of unfired pressure vessels and shall carry its approval stamp. (a) The tank shall be located above normal ground surface and shall be fenced to protect it from vandalism.(b) Sizing--For surface and ground water systems where the pump yield equals or exceeds the instantaneous demand, the tank shall be sized so the pump cycles a maximum of six (6) times per hour. Where the pump yield is less than the instantaneous demand the tank shall be sized to provide the difference for a minimum twenty (20) minute demand period based on the actual usable volume of the tank.(c) Bypass Piping--A flow through arrangement is required for all hydropneumatic storage tanks. However, the tank shall also be equipped with bypass piping to permit the tank to be removed from service for repairs or painting without removing well(s) or booster pump(s) from service. Bypass piping is not required for tanks less than 500 gallons.(d) Appurtenances--All hydropneumatic tanks shall be equipped with a drain, isolation valves, sample tap, pressure gauge, air make-up system (except for bladder tanks), pressure relief valve, and pressure operated start and stop controls for the pump. Each tank five hundred (500) gallons and larger shall have an access manhole, a minimum two (2) inch diameter drain, and a vacuum relief valve. An air compressor is required on tanks two thousand (2000) gallons and larger.(e) Freezing--All hydropneumatic storage tanks and their appurtenances shall be designed to prevent freezing which will interfere with proper functioning.(f) Painting and/or cathodic protection--Proper protection shall be given to metal surfaces by paints or other protective coatings, by cathodic protective devices, or by both. All paint coatings which come into contact with drinking water shall be certified as meeting the specifications of the American National Standard Institute/National Sanitation Foundation Standard 61, Drinking Water System Components--Health Effects. The certifying party shall be accredited by the American National Standards Institute. Hot applied wax, cold applied wax, grease, and coal tar coatings are not acceptable.(g) Disinfection--Hydropneumatic storage tanks shall be disinfected in accordance with current American Waterworks Association (AWWA) Standard for the disinfection of water storage facilities. Prior to sampling, the chlorine residual must be reduced to normal system residual levels or be non-detectable in those systems not chlorinating. A minimum of two (2) samples must be collected and analyzed for total coliform bacteria. These samples must be collected at least twenty-four (24) hours apart and results must show the absence of total coliform bacteria. The chlorine residual must also be measured and reported. If the membrane filter method of analysis is used for the coliform analysis, non-coliform growth must also be reported. If the non-coliform growth is greater than eighty (80) colonies per one hundred (100) ml, the sample result is invalid and must be repeated. All samples must be analyzed by a certified laboratory. The Department may request that heterotrophic plate count analyses be conducted on a case-by-case basis where disinfection problems are suspected.(h) The pressure range of hydropneumatic tanks shall not exceed twenty (20) pounds per square inch.S.C. Code Regs. § 61-58.4.C