A public water system that uses a surface water source shall meet all of the conditions of paragraphs (1) and (2) of this section, and is subject to paragraph (3) of this section, beginning December 30, 1991, unless the Department has determined, in writing, that filtration is required. A public water system that uses a ground water source under the direct influence of surface water shall meet all of the conditions of paragraphs (1) and (2) of this section and is subject to paragraph (3) of this section, beginning 18 months after the Department determines that it is under the direct influence of surface water, or December 30, 1991, whichever is later, unless the Department has determined, in writing, that filtration is required. If the Department determines, in writing, before December 30, 1991, that filtration is required, the system shall have installed filtration and meet the criteria for filtered systems specified in R.61-58.10(D)(2)(D)(2) and R.61-58.10(D)(2)(E)by June 61-58.10(D)(2)9, 1993. Within 18 months of the failure of a system using surface water or a ground water source under the direct influence of surface water to meet any one of the requirements of paragraphs (1) and (2) of this section or after June 29, 1993, whichever is later, the system shall have installed filtration and meet the criteria for filtered systems specified inR.61-58.10(E)(D)(2) and R.61-58.10(E).
(1) Source water quality conditions. (a) The fecal coliform concentration must be equal to or less than 20/100 ml, or the total coliform concentration must be equal to or less than 100/100 ml [measured as specified in R.61-58.10(F)(1)(a) and (b) and (2)(a)(F)(1)(a) and (b) and (2)(a)], in representative samples of the source water immediately prior to the first or only point of disinfectant application in at least 90 percent of the measurements made for the 6 previous months that the system served water to the public on an ongoing basis. If a system measures both fecal and total coliforms, the fecal coliform criterion, but not the total coliform criterion, in this paragraph must be met.(b) The turbidity level cannot exceed 5 NTU [measured as specified in R.61-58.10(F)(1)(d) and (2)(b)(F)(1)(d) and (2)(b)] in representative samples of the source water immediately prior to the first or only point of disinfectant application unless: (i) The Department determines that any such event was caused by circumstances that were unusual and unpredictable; and(ii) As a result of any such event, there have not been more than two events in the past 12 months the system served water to the public, or more than five events in the past 120 months the system served water to the public, in which the turbidity level exceeded 5 NTU. An "event" is a series of consecutive days during which at least one turbidity measurement each day exceeds 5 NTU.(2) Site-specific conditions. (a)(i) The public water system shall meet the requirements of R.61-58.10(D)(1)(a)(D)(1)(a)at least 11 of the 12 previous months that the system served water to the public, on an ongoing basis, unless the system fails to meet the requirements during 2 of the 12 previous months that the system served water to the public, and the Department determines that at least one of these failures was caused by circumstances that were unusual and unpredictable.(ii) The public water system shall meet the requirements of R.61-58.10(D)(1)(b)(D)(1)(b)at all times the system serves water to the public.(iii) The public water system shall meet the requirements of R.61-58.10(D)(1)(c)(D)(1)(c)at all times the system serves water to the public unless the Department determines that any such failure was caused by circumstances that were unusual and unpredictable.(iv) The public water system shall meet the requirements of R.61-58.10(D)(1)(d)(D)(1)(d)on an ongoing basis unless the Department determines that failure to meet these requirements was not caused by a deficiency in treatment of the source water.(b) The public water system shall maintain a watershed control program which minimizes the potential for contamination by Giardia lamblia cysts and viruses in the source water. The Department shall determine whether the watershed control program is adequate to meet this goal. The adequacy of a program to limit potential contamination by Giardia lamblia cysts and viruses shall be based on: the comprehensiveness of the watershed review; the effectiveness of the system's program to monitor and control detrimental activities occurring in the watershed; and the extent to which the water system has maximized land ownership and/or controlled land use within the watershed. At a minimum, the watershed control program shall; (i) Characterize the watershed hydrology and land ownership;(ii) Identify watershed characteristics and activities which may have an adverse effect on source water quality; and(iii) Monitor the occurrence of activities which may have an adverse effect on source water quality. The public water system shall demonstrate through ownership and/or written agreements with landowners within the watershed that it can control all human activities which may have an adverse impact on the microbiological quality of the source water. The public water system shall submit an annual report to the Department that identifies any special concerns about the watershed and how they are being handled; describes activities in the watershed that affect water quality; and projects what adverse activities are expected to occur in the future and describes how the public water system expects to address them. For systems using a ground water source under the direct influence of surface water, an approved wellhead protection program developed under section1428 of the Federal Safe Drinking Water Act may be used, if the Department deems it appropriate, to meet these requirements.
(c) The public water system shall be subject to an annual on-site inspection to assess the watershed control program and disinfection treatment process. Either the Department or a party approved by the Department shall conduct the on-site inspection. The inspection shall be conducted by competent individuals such as sanitary and civil engineers, sanitarians, or technicians who have experience and knowledge about the operation and maintenance of a public water system, and who have a sound understanding of public health principles and waterborne diseases. A report of the on-site inspection summarizing all findings shall be prepared every year. The on-site inspection shall indicate to the Department's satisfaction that the watershed control program and disinfection treatment process are adequately designed and maintained. The on-site inspection shall include: (i) A review of the effectiveness of the watershed control program;(ii) A review of the physical condition of the source intake and how well it is protected;(iii) A review of the system's equipment maintenance program to ensure there is low probability for failure of the disinfection process;(iv) An inspection of the disinfection equipment for physical deterioration;(v) A review of operating procedures;(vi) A review of data records to ensure that all required tests are being conducted and recorded and disinfection is effectively practiced; and(vii) Identification of any improvements which are needed in the equipment, system maintenance and operation, or data collection.(d) The public water system shall not have been identified as a source of a waterborne disease outbreak, or if it has been so identified, the system shall have been modified sufficiently to prevent another such occurrence, as determined by the Department.(e) The public water system shall comply with the maximum contaminant level (MCL) for total coliforms in R.61-58.5.F(1) and (2) and the MCL for E. coli in R.61-58.5.F(3) at least 11 months of the 12 previous months that the system served water to the public, on an ongoing basis, unless the Department determines that failure to meet this requirement was not caused by a deficiency in treatment of the source water.(f) The public water system must comply with the requirements for trihalomethanes in R.61-58.13.(3) Treatment technique violations. (a) A system is in violation of a treatment technique requirement if: (i) it fails to meet any one of the criteria in paragraphs (1) and (2) of this section and/or the Department has determined, in writing, that filtration is required; and(ii) it fails to install filtration by the date specified in the introductory paragraph of this section.(b) A system that has not installed filtration is in violation of a treatment technique requirement if: (i) The turbidity level [measured as specified in R.61-58.10(F)(1)(d) and (2)(b)(F)(1)(d) and (2)(b)] in a representative sample of the source water immediately prior to the first or only point of disinfection application exceeds 5 NTU; or(ii) The system is identified as a source of a waterborne disease outbreak.S.C. Code Regs. § 61-58.10.C
Amended by State Register Volume 38, Issue No. 9, eff. 9/26/2014.