S.C. Code Regs. § § 61-17.1900.1906

Current through Register Vol. 48, 12, December 27, 2024
Section 61-17.1900.1906 - Utility Rooms (II)
A. At least one (1) soiled utility room per staff work area shall be provided that contains a clinical sink, work counter, and waste receptacle. As an exception, the clinical sink shall not be required if each resident toilet is equipped with bedpan cleaning lugs, spray hose and elevated vacuum breaker.
B. At least one (1) clean utility room per staff work area shall be provided that contains a work counter with handwashing sink and space for the storage and assembly of supplies for nursing procedures.

S.C. Code Regs. § 61-17.1900.1906

Renumbered from 61-17.2800.2811 State Register Volume 40, Issue No. 03, eff. 3/25/2016.