Section 61-13.2300.2304 - Receptacles (II)A. A facility shall provide duplex grounding type receptacles in each client room with one (1) duplex receptacle at the head of each bed in compliance with provisions of the codes officially adopted by the South Carolina Building Codes Council and the South Carolina State Fire Marshal.B. Each client bed location shall have a minimum of two (2) duplex receptacles.C. Each client bed location shall be supplied by at least two (2) branch circuits.D. Duplex receptacles for general use shall be installed approximately fifty (50) feet apart in all corridors and within twenty-five (25) feet of the ends of corridors.S.C. Code Regs. § 61-13.2300.2304
Added by State Register Volume 40, Issue No. 05, eff. 5/27/2016.