Section 61-13.1900.1901 - Fire Alarms and SprinklersA. A facility shall include a partial, manual, automatic, and supervised fire alarm system. A facility shall arrange the fire alarm system to transmit an alarm automatically to a third party by an approved method. A facility shall provide a fire alarm system that notifies all occupiable areas and floors of the building by audible and visual alarm. A facility shall provide a fire alarm system that shuts down central recirculating systems and outside air units that serve the area(s) of alarm origination at a minimum.B. A facility shall include all fire, smoke, heat, sprinkler flow, or manual fire alarming devices or systems that connect to the main fire alarm system and triggers the system when activated.C. A facility shall include a sprinkler system.D. A facility shall include a fire alarm pull station in or near each control station.S.C. Code Regs. § 61-13.1900.1901