Current through Register Vol. 48, No. 10, October 25, 2024
Section 61-107.279.G.64 - Used Oil Storagea. Used oil burners may not store used oil in units other than tanks, containers, or units subject to regulation under R.61-79.264 or 265.b. Containers and aboveground tanks used to store used oil at burner facilities must be: (1) In good condition (no severe rusting, apparent structural defects or deterioration); and(2) Not leaking (no visible leaks).c. Containers and tanks used to store used oil at burner facilities must be equipped with a secondary containment system capable of retaining the volumetric contents of the largest container. (1) The secondary containment system must consist of, at a minimum:(a) Dikes, berms or retaining walls; and(b) A floor. The floor must cover the entire area within the dike, berm, or retaining wall.(2) The entire containment system, including walls and floor, must be sufficiently impervious to used oil to prevent any used oil released into the containment system from migrating out of the system to the soil, groundwater, or surface water.d. Existing aboveground tanks used to store used oil at burner facilities must be equipped with a secondary containment system capable of retaining the volumetric contents of the largest tank. (1) The secondary containment system must consist of, at a minimum:(a) Dikes, berms or retaining walls; and(b) A floor. The floor must cover the entire area within the dike, berm, or retaining wall except areas where existing portions of the tank meet the ground; or(c) An equivalent secondary containment system approved by the Department.(2) The entire containment system, including walls and floor, must be sufficiently impervious to used oil to prevent any used oil released into the containment system from migrating out of the system to the soil, groundwater, or surface water.e. New aboveground tanks used to store used oil at burner facilities must be equipped with a secondary containment system capable of retaining the volumetric contents of the largest tank. (1) The secondary containment system must consist of, at a minimum:(a) Dikes, berms or retaining walls; and(b) A floor. The floor must cover the entire area within the dike, berm, or retaining wall; or(c) An equivalent secondary containment system approved by the Department.(2) The entire containment system, including walls and floor, must be sufficiently impervious to used oil to prevent any used oil released into the containment system from migrating out of the system to the soil, groundwater, or surface water.f. Labels. (1) Containers and aboveground tanks used to store used oil at burner facilities must be labeled or marked clearly with the words "Used Oil."(2) Fill pipes used to transfer used oil into underground storage tanks at burner facilities must be labeled or marked clearly with the words "Used Oil."g. Upon detection of a release of used oil to the environment not subject to the requirements of R.61-92.280 Subpart F, a burner must perform the following cleanup steps: (2) Contain the released used oil;(3) Clean up and manage properly the released used oil and other materials; and(4) If necessary, repair or replace any leaking used oil storage containers or tanks prior to returning them to service.(5) Further assessment and remediation, if necessary, shall be directed by the Department.h. Used oil burners are subject to all applicable Spill Prevention, Control and Countermeasures ( 40 CFR Part 112 ) in addition to the requirements of this subpart. Used oil generators are also subject to R.61-92.280 standards for used oil stored in underground tanks whether or not the used oil exhibits any characteristics of hazardous waste, in addition to the requirements of this subpart.S.C. Code Regs. § 61-107.279.G.64
Added by State Register Volume 19, Issue No. 7, eff July 28, 1995.