Current through December 26, 2024
Section 250-RICR-140-25-2.9 - Boiler Rooms and Remote Fill TanksA. Within one (1) year of the effective date of these Regulations the owner and operator of a facility shall:1. Install oil traps or manually operated drain valves, or eliminate drains from boiler rooms. All oil traps shall be adequately maintained and cleaned. All drain valves shall be maintained in the closed position except when the operator is in the process of draining oil-free clean water in compliance with all applicable State and Federal Regulations.2. All above ground and underground storage tanks with a remote fill and a capacity greater than five hundred (500) gallons shall be equipped with a high-level warning alarm system.3. All tanks with a capacity greater than five hundred (500) gallons shall be equipped with spill containment around fill areas.250 R.I. Code R. 250-RICR-140-25-2.9
Amended effective 5/2/2018
Amended effective 7/20/2022