250 R.I. Code R. 250-RICR-120-05-53.6

Current through December 26, 2024
Section 250-RICR-120-05-53.6 - Prohibited Substances
A. The following tables list prohibited substances in specific end-uses and the effective date of prohibition, unless an exemption is provided for in § 53.5 of this Part. The prohibitions do not apply to products and equipment in specific enduses manufactured prior to an applicable effective date.
1. End-use and Prohibited Substances
a. Table 2: End-Use Category: Aerosol Propellants

End-Use

Prohibited Substances

Effective Date

Aerosol Propellants

HFC-125, HFC-134a, HFC-227ea and blends of HFC-227ea and HFC-134a

January 1, 2022

b. Table 3: End-Use Category: Air Conditioning

End-Use

Prohibited Substances

Effective Date

Centrifugal chillers (new)

FOR12A, FOR12B, HFC-134a, HFC-227ea, HFC-236fa, HFC245fa, R-125/ 134a/ 600a (28.1/70/1.9), R-125/ 290/ 134a/ 600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-423A, R-424A, R-434A, R-438A, R-507A, RS-44 (2003 composition), THR-03

January 1, 2024

Positive displacement chillers (new)

FOR12A, FOR12B, HFC-134a, HFC-227ea, KDD6, R-125/ 134a/ 600a (28.1/70/1.9), R-125/ 290/ 134a/ 600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-424A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 composition), SP34E, THR-03

January 1, 2024

c. Table 4: End-Use Category: Refrigeration

End-Use

Prohibited Substances

Effective Date

Cold storage warehouses (new)

HFC-227ea, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-423A, R-424A, R-428A, R-434A, R-438A, R-507A, RS-44 (2003 composition)

January 1, 2023

Household refrigerators and freezers (new)

FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03

January 1, 2022

Household refrigerators and freezers-compact (new)

FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03

January 1, 2022

Household refrigerators and freezers-built in appliances (new)

FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03

January 1, 2023

Supermarket Systems (Retrofit)

R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A

January 1, 2022

Supermarket Systems (New)

HFC-227ea, R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A

January 1, 2022

Remote Condensing Units (Retrofit)

R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A

January 1, 2022

Remote Condensing Units (New)

HFC-227ea, R-404A, R-407B, R-421B, R-422A, R-422C, R-422D, R-428A, R-434A, R-507A

January 1, 2022

Stand-Alone Units (Retrofit)

R-404A, R-507A

January 1, 2022

Stand-Alone Medium Temperature Units (New)

FOR12A, FOR12B, HFC-134a, HFC-227ea, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), RS-44 (2003 formulation), SP34E, THR-03

January 1, 2022

Stand-Alone Low-Temperature Units (New)

HFC-227ea, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 formulation)

January 1, 2022

Refrigerated food processing and dispensing equipment (New)

HFC-227ea, KDD6, R-125/ 290/ 134a/ 600a (55.0/1.0/42.5/1.5), R-404A, R-407A, R-407B, R-407C, R-407F, R-410A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R424A, R-428A, R-434A, R-437A, R-438A, R-507A, RS-44 (2003 formulation)

January 1, 2022

Vending Machines (Retrofit)

R-404A, R-507A

January 1, 2022

Vending Machines (New)

FOR12A, FOR12B, HFC-134a, KDD6, R-125/290/134a/600a (55.0/1.0/42.5/1.5), R-404A, R407C, R-410A, R-410B, R-417A, R-421A, R-422B, R-422C, R-422D, R-426A, R-437A, R-438A, R-507A, RS-24 (2002 formulation), SP34E

January 1, 2022

d. Table 5: End-Use Category: Foams

End-Use

Prohibited Substances

Effective Date

Rigid Polyurethane and Polyisocyanurate Laminated Boardstock

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof

January 1, 2022

Flexible Polyurethane

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof

January 1, 2022

Integral Skin Polyurethane

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Polystyrene Extruded Sheet

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Phenolic Insulation Board and Bunstock

HFC-143a, HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof

January 1, 2022

Rigid Polyurethane Slabstock and Other

HFC-134a, HFC-245fa, HFC-365mfc and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Rigid Polyurethane Appliance Foam

HFC-134a, HFC-245fa, HFC-365mfc and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Rigid Polyurethane Commercial Refrigeration and Sandwich Panels

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Polyolefin

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Rigid Polyurethane Marine Flotation Foam

HFC-134a, HFC-245fa, HFC-365mfc and blends thereof; Formacel TI, Formacel Z-6

January 1, 2022

Polystyrene Extruded Boardstock and Billet (XPS)

HFC-134a, HFC-245fa, HFC-365mfc, and blends thereof; Formacel TI, Formacel B, Formacel Z-6

January 1, 2022

Rigid polyurethane (PU) high-pressure two-component spray foam

HFC-134a, HFC-245fa, and blends thereof; blends of HFC-365mfc with at least 4 percent HFC-245fa, and commercial blends of HFC-365mfc with 7 to 13 percent HFC-227ea and the remainder HFC-365mfc; Formacel TI

January 1, 2022

Rigid PU low-pressure two-component spray foam

HFC-134a, HFC-245fa, and blends thereof; blends of HFC-365mfc with at least 4 percent HFC-245fa, and commercial blends of HFC-365mfc with 7 to 13 percent HFC-227ea and the remainder HFC-365mfc; Formacel TI

January 1, 2022

Rigid PU one-component foam sealants

HFC-134a, HFC-245fa, and blends thereof; blends of HFC-365mfc with at least 4 percent HFC-245fa, and commercial blends of HFC-365mfc with 7 to 13 percent HFC-227ea and the remainder HFC-365mfc; Formacel TI

January 1, 2022

250 R.I. Code R. 250-RICR-120-05-53.6

Adopted effective 8/1/2021