C = Pv x 15,000/8,500
Where:
C = HMIWI capacity, lb/hr
Pv = primary chamber volume, ft3
15,000 = primary chamber heat release factor, Btu/ft3/hr
8,500 = standard waste heating value, Btu/lb;
C = Pv x 4.5/8
Where:
C = HMIWI capacity, lb/hr
Pv = primary chamber volume, ft3
4.5 = waste density, lb/ft3
8 = typical hours of operation of a batch HMIWI, hours.
250 R.I. Code R. 250-RICR-120-05-39.5