6 Pa. Code § 11.86

Current through Register Vol. 54, No. 49, December 7, 2024
Section 11.86 - Fire alarm
(a) There shall be an operable fire alarm system that is audible throughout the building.
(b) If one or more clients have deafness or a hearing impairment, the center shall do one of the following:
(1) Equip the fire alarm system with visual alarm devices.
(2) Establish written procedures for the evacuation of clients with deafness or a hearing impairment and incorporate them into the emergency evacuation procedures in § 11.82 (relating to evacuation procedures).
(c) If the fire alarm is inoperative, repairs shall be made within 2 working days of the time the fire alarm was found to be inoperative.
(d) There shall be a written procedure for fire safety monitoring in the event the fire alarm is inoperative.

6 Pa. Code § 11.86

This section cited in 6 Pa. Code § 11.212 (relating to applicability).