34 Pa. Code § 39.106

Current through Register Vol. 54, No. 45, November 9, 2024
Section 39.106 - Isolating live parts by elevation

Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:

Voltage of ConductorsElevation (in feet)
300-750 7
750-2,500 7
2,500-7,500 8
7,500-30,000 9
30,000-70,00010
70,000-100,00012
Over 100,00014

34 Pa. Code § 39.106

This section cited in 34 Pa. Code § 39.143 (relating to isolation by elevation); 34 Pa. Code § 39.160 (relating to guarding live parts of switches and automatic cut-outs not installed on switchboards); and 34 Pa. Code § 39.199 (relating to guarding or isolating live parts).