34 Pa. Code § 14a.101

Current through Register Vol. 54, No.43, October 26, 2024
Section 14a.101 - Storage
(a) Class I liquids shall be stored in closed containers or in storage tanks aboveground outside of buildings, or underground.
(b) Class II or class III liquids shall be stored in containers or in tanks within buildings, aboveground outside of buildings, or underground.
(c) Outside container storage shall be in accordance with § 14a.46 (relating to storage outside of buildings).
(d) The use of an underground tank for bulk plant storage purposes in lieu of the purpose for which it was originally installed and approved, such as service station tanks, is prohibited. Exceptions will be made where the requirements of this subpart are met, that is, loading rack distance requirements to property lines and buildings, pump and daily gauging requirements, and the like, and a written approval has been issued based on proper application and drawings submitted for the use of the tank and related pumping equipment as a bulk plant.

34 Pa. Code § 14a.101

The provisions of this § 13.101 amended June 22, 1984, effective 6/18/1984, 14 Pa.B. 2131; transferred from 37 Pa. Code and renumbered as 34 Pa. Code §14a.101, February 28, 2014, effective 3/1/2014, 44 Pa.B. 1233.