Current through Register Vol. 54, No. 49, December 7, 2024
Section 205.33 - Utility room(a) Provisions shall be made in each nursing unit near the nurses' station for utility rooms. The area shall have separate soiled and clean workrooms. The rooms may not be more than 120 feet from the most remote room served. If one nursing station services several resident corridors, a soiled utility room shall be on each unit.(b) Facilities for flushing and rinsing bedpans, such as a spray attachment for the clinical sink or a separate bedpan flusher, shall be provided in the soiled workroom of each nursing unit, unless bedpan flushing devices, together with bedpan lugs on toilets are provided in each resident's toilet for this purpose.(c) Hand-washing facilities shall be available in the soiled and clean utility rooms.The provisions of this § 205.33 adopted August 29, 1975, effective 9/1/1975, 5 Pa.B. 2233; amended January 31, 1987, effective 7/1/1987, 17 Pa.B. 514; amended July 23, 1999, effective 7/24/1999, 29 Pa.B. 3999.The provisions of this § 205.33 amended under section 803 of the Health Care Facilities Act (35 P. S. § 448.803); and section 2102(g) of The Administrative Code of 1929 (71 P. S. § 532(g)).