Current through Vol. 42, No. 8, January 2, 2025
Section 748:20-4-16 - IFC[®] 2018 Chapter 11 Construction Requirements for Existing BuildingsChapter 11 of the Oklahoma adopted IFC® 2018 is adopted with the following modifications:
(1) Section 1103.4.2 Three to five stories. This section has been modified to add a fifth exception to provide relief from this section of the code when vertical openings comply with the requirements of Section 803.2.1 of the IEBC®. This section has been modified to read: 1103.4.2 Three to five stories. In other than Group I-2 and I-3 occupancies, interior vertical openings connecting three to five stories shall be protected by either 1-hour fire-resistant-rated construction or an automatic sprinkler system shall be installed throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2. Exceptions: (A) Vertical opening protection is not required for Group R-3 occupancies.(B) Vertical opening protection is not required for open parking garages.(C) Vertical opening protection for escalators shall be in accordance with Section 1103.4.5, 1103.4.6 or 1103.4.7. (D) Exit access stairways and ramps shall be in accordance with Section 1103.4.8.(E) Vertical openings that comply with the requirements of Section 802.2.1 of the IEBC®.(2) Section 1103.7.6 Group R-2. This section has been modified to address errata published by the ICC. The correction is in the last exception and requires each dwelling unit to be provided with smoke alarms complying with the requirements of Section 907.2.10. This section has been modified to read: 1103.7.6 Group R-2. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in existing Group R-2 occupancies more than three stories in height or with more than 16 dwelling or sleeping units. Exceptions: (A) Where each living unit is separated from other contiguous living units by fire barriers having a fire-resistance rating of not less than 3/4 hour, and where each living unit has either its own independent exit or its own independent stairway or ramp discharging at grade. (B) A separate fire alarm system is not required in buildings that are equipped throughout with an approved supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and having a local alarm to notify all occupants. (C) A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress doors opening directly to an exterior exit access that leads directly to the exits or are served by open ended corridors designed in accordance with Section 1027.6, Exception 3.(D) A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units, do not exceed three stories in height and comply with both of the following: (i) Each dwelling unit is separated from other contiguous dwelling units by fire barriers having a fire-resistance rating of not less than 3/4 hour.(ii) Each dwelling unit is provided with smoke alarms complying with the requirements of Section 907.2.10.(3) Section 1104.25 Egress path markings. This section, including the exception, has been moved and renumbered into the newly created Appendix O, entitled "Egress Path Markings for Existing Buildings" and is not adopted as a minimum standard for residential or commercial fire prevention and fire protection systems within the State of Oklahoma. The section number 1104.25 itself, will stay as part of this code for numbering alignment but will not have any requirements attached to it.Okla. Admin. Code § 748:20-4-16
Reserved by Oklahoma Register, Volume 37, Issue 24, September 1, 2020, eff. 8/3/2020Adopted by Oklahoma Register, Volume 38, Issue 24, September 1, 2021, eff. 9/14/2021