Current through Vol. 42, No. 6, December 2, 2024
Section 380:25-5-12 - Water level indicators(a) No outlet connections (except for damper regulator, feedwater regulator, low water fuel cutout, drains, steam gauges, or such apparatus that does not permit the escape of an appreciable amount of steam or water therefrom) shall be placed on the piping that connects the water column to the boiler. The water column shall be provided with a valved drain of at least 3/4 inch pipe size, the discharge to be piped to a safe location.(b) For all installations where the water gauge glass or glasses are more than 30 feet above the boiler operating floor, it is recommended that remote water level indicating or recording gauges be installed at eye height above the operating floor.Okla. Admin. Code § 380:25-5-12
Amended at 16 Ok Reg 3017, eff 7-12-99