Okla. Admin. Code § 252:656-5-1

Current through Vol. 41, No. 19, June 17, 2024
Section 252:656-5-1 - Design capacity

Design sewers for the ultimate future population that may be served.

(1) Consider the maximum hourly domestic flow, industrial flow, inflow and infiltration and the topography regarding the slope and pumping needs.
(2) Design for an average daily per capita flow of 100 gpd, which includes normal infiltration. Peak design flow must be based on an acceptable infiltration/inflow (I/I) study or, for new sewer extensions, the ratio of peak to average daily flow from a widely recognized engineering standard.
(3) Exclude storm water from roof drains, streets and other areas.

Okla. Admin. Code § 252:656-5-1

Added at 17 Ok Reg 1140, eff 6-1-00; Amended at 23 Ok Reg 937, eff 6-15-06