(a)Concrete tanks. Concrete tanks shall be reinforced with rebar or fiber, and constructed of a mix which demonstrates a twenty-eight-day compressive strength of four (4) thousand pounds per square inch (4,000 psi). They may be poured in place or precast, but, in either case, shall be monolithically poured and mechanically vibrated.
(b)Fiberglass and plastic tanks. Fiberglass and plastic tanks shall meet either IAPMO or CSA standards for septic tanks and shall be installed according to the manufacturer's recommendations. If the tank does not bear the IAPMO or CSA mark, then DEQ will require the installer to submit documentation from IAPMO or CSA stating the tank meets the above standards.