Okla. Admin. Code § 252:515-23-55

Current through Vol. 41, No. 19, June 17, 2024
Section 252:515-23-55 - Monitoring
(a)Monitoring required. The incinerator shall have continuous monitoring and recording for waste feed, fuel and combustion gas flows; oxygen and carbon monoxide, and temperature.
(b)Instrument calibration. Monitoring devices shall be routinely calibrated in accordance with manufacturer's recommendations.
(c)DEQ may monitor. Incinerators shall have the capability for the DEQ to connect its own monitoring or calibration test equipment.
(d)Monitoring data retention. Monitoring data shall be maintained for at least two years.
(e)Excursions. In the event more than thirty excursions from the operating parameters occur within any calendar month, the owner/operator shall shut down operations until such time as repairs are made and documented engineering analysis shows how the cause has been corrected.

Okla. Admin. Code § 252:515-23-55

Added at 20 Ok Reg 1151, eff 6-1-03