Okla. Admin. Code § 252:100-17-19

Current through Vol. 42, No. 1, September 16, 2024
Section 252:100-17-19 - Standards for municipal waste combustor organics expressed as total mass dioxins/furans
(a) The concentration of organics, expressed as total mass dioxins/furans, contained in the gases discharged to the atmosphere from a MWC unit shall not exceed:
(1) Before April 28, 2009, with electrostatic precipitator: 60 nanograms per dry standard cubic meter (total mass), corrected to 7 percent oxygen.
(2) By April 28, 2009, with electrostatic precipitator: 35 nanograms per dry standard cubic meter (total mass), corrected to 7 percent oxygen.
(3) Without electrostatic precipitator: 30 nanograms per dry standard cubic meter (total mass), corrected to 7 percent oxygen.
(b) MWC units that achieve a dioxin/furan emission level less than or equal to 15 nanograms per dry standard cubic meter total mass, corrected to 7 percent oxygen, may elect the alternative performance testing schedule for dioxins/furans as specified in 40 CFR 60.58b(g)(5)(iii).

Okla. Admin. Code § 252:100-17-19

Added at 15 Ok Reg 2591, eff 6-25-98; Amended at 26 Ok Reg 1165, eff 7-1-09