NITROGEN OXIDES LIMITS | |||
Municipal waste combustor technology | Nitrogen oxides emission limit (ppm by volume) a | ||
Before | On or After | ||
April 28, 2009 | |||
Mass burn waterwall | 205 | 205 | |
Mass burn rotary waterwall | 250 | 210 | |
Refuse-derived fuel combustor | 250 | 250 | |
Fluidized bed combustor(by December 19, 2000) | 240 | ||
Fluidized bed combustor(by August 26, 2002, or three years after EPA approval of the State plan, which ever is first) | 180 | 180 | |
Mass burn refractory combustors | No limit | No limit | |
a Corrected to 7 percent oxygen, dry basis, 24 hr daily arithmetic average | |||
NITROGEN OXIDES LIMITS FOR EXISTING DESIGNATED FACILITIES INCLUDED IN AN EMISSIONS AVERAGING PLAN AT A MUNICIPAL WASTE COMBUSTOR PLANT a | |||
Municipal waste combustor technology | Nitrogen oxides emission limit (ppm by volume) b | ||
Before | On or After | ||
April 28, 2009 | |||
Mass burn waterwall | 185 | 185 | |
Mass burn rotary waterwall | 220 | 190 | |
Refuse-derived fuel combustor | 230 | 230 | |
Fluidized bed combustor | 165 | 165 | |
a Mass burn refractory municipal waste combustors and other MWC technologies not listed above may not be included in an emissions averaging plan. | |||
b Corrected to 7 percent oxygen, dry basis, 24 hr daily arithmetic average | |||
Okla. Admin. Code § 252:100-17-20