Okla. Admin. Code § 165:35-15-17

Current through Vol. 41, No. 19, June 17, 2024
Section 165:35-15-17 - Schedule for testing demand meters

The following schedule is required for testing demand meters:

(1) Block interval demand-registers-equipped watt-hour meters.
(A) Meters with surge-proof magnets - 12 years.
(B) Meters without surge-proof magnets - 8 years.
(2) Block interval graphic watt-hour demand meters - 2 years.
(3) Lagged demand meters - 8 years.
(4) Pulse recorders and pulse-operated demand meters in combination with pulse-initiator-equipped watt-hour meters - 2 years. If a comparison is made between the meter registration and the recorder registration each billing period, and the recorder registration agrees within one percent (1%) of that registered by the associated meter, the schedule for pulse recorders and pulse-operated demand meters should be as indicated in (A) and (B) of this paragraph. If recorder meter registration checks do not agree within one percent (1%), the demand metering equipment should be tested.
(A) Meters with surge-proof magnets - 16 years.
(B) Meters without surge-proof magnets - 8 years.

Okla. Admin. Code § 165:35-15-17

Amended at 10 Ok Reg , eff 6-25-93