Okla. Admin. Code § 165:25-8-36

Current through Vol. 42, No. 4, November 1, 2024
Section 165:25-8-36 - Fire extinguishers
(a) Each marina must have a 40B:C fire extinguisher.
(b) A minimum of three extinguishers must be located at the fuel dock, and one or more must be located within 50 feet (50' or 15 meters) of each pump, dispenser, and underground fill pipe opening.
(c) Piers that extend more than 500 feet (500' or) one hundred fifty-two meters (152 m) in travel distance from shore must have a Class III standpipe installed in accordance with NFPA 14, Standard for the Installation of Standpipe and Hose Systems.
(d) There must be a knife readily accessible at the fuel dock for quickly cutting mooring lines in an emergency and a push pole for shoving away a boat.

Okla. Admin. Code § 165:25-8-36

Added at 18 Ok Reg 2378, eff 7-1-01; Amended at 21 Ok Reg 2036, eff 7-1-04; Amended at 22 Ok Reg 1730, eff 7-1-05; Amended at 23 Ok Reg 137, eff 10-6-05 (emergency); Amended at 23 Ok Reg 2261, eff 7-1-06; Amended at 25 Ok Reg 1867, eff 7-1-08
Amended by Oklahoma Register, Volume 36, Issue 21, July 15, 2019, eff. 8/1/2019