(C) Transmission and distribution facilities inspections. Unless otherwise determined by the commission, each electric utility and transmission owner shall, at a minimum, inspect its electric transmission and distribution facilities (circuits and equipment) to maintain quality, safe, and reliable service on the following scheduled basis:
(1) Distribution - all distribution circuits and equipment, including above-ground facilities associated with the operation of underground circuits, shall be inspected at least once every five years.(2) Transmission - all transmission circuits and equipment shall be inspected at least once every year.(3) Substations - all transmission and distribution substations and equipment shall be inspected twelve times annually, with no inspection interval exceeding forty calendar days between inspections.(4) On or before March thirty-first of each year, each electric utility and transmission owner shall submit a report in an electronic medium, in a format prescribed by the commission or its staff, of the electric utility's and/or transmission owner's compliance with the inspection schedule in paragraphs (D)(1) to (D)(3) of this rule for the preceding calendar year. The annual report of inspection compliance shall include:(a) A listing of distribution circuits inspected during the year and, for each listed circuit, the date(s) such inspection was performed.(b) A listing of transmission circuits inspected during the year and, for each listed circuit, the date(s) such inspections were performed.(c) A listing of all substations and the date of each inspection during the year.(d) The date(s) when any circuits or substations were added or retired during the reporting year.