Before an employee moves or operates power cranes, shovels, backhoes or any other type of material hoisting equipment within ten feet of an energized electrical conductor, the employer will:
Table 23-1
ALTERNATING CURRENT - MINIMUM DISTANCES
Voltage Range (phase to phase) kilovolt | Minimum Working and Clear Hot Stick Clearance |
2.1 to 15 | 2 ft. 0 in. |
15.1 to 35 | 2 ft. 4 in. |
35.1 to 46 | 2 ft. 6 in. |
46.1 to 72.5 | 3 ft. 0 in. |
72.6 to 121 | 3 ft. 4 in. |
133 to 145 | 3 ft. 6 in. |
161 to 169 | 3 ft. 8 in. |
230 to 242 | 5 ft. 0 in. |
345 to 362 | *7 ft. 0 in. |
500 to 552 | *11 ft. 0 in |
700 to 765 | *15 ft. 0 in |
* NOTE: For 345-362kv. 500-552kv. and 700-765kv. the minimum working distance and the minimum clear hot stick distance may be reduced provided that such distances are not less than the shortest distance between the energized part and a grounded surface.
Table 23-2
Approach Distances to Exposed Energized Overhead Power Lines and Parts
Voltage range (phase to phase, RMS) | Approach distance (inches) |
300 V and less | (1) |
Over 300V, not over 750V | 12 |
Over 750V not over 2kV | 18 |
Over 2kV, not over 15kV | 24 |
Over 15kV, not over 37kV | 36 |
Over 37kV, not over 87.5kV | 42 |
Over 87.5kV, not over 121kV | 48 |
Over 121kV, not over 140kV | 54 |
1Avoid contact.
Ohio Admin. Code 4123:1-5-23
Five Year Review (FYR) Dates: 11/1/2027
Promulgated Under: 119.03
Statutory Authority: 4121.12, 4121.121, 4121.13
Rule Amplifies: 4121.47
Prior Effective Dates: 01/01/1986, 04/10/2011, 02/01/2022