[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
DESIGN CRITERIA
TABLE 301.2.1.2
WINDBORNE DEBRIS PROTECTION FASTENING SCHEDULE FOR WOOD STRUCTURAL PANELS
Deleted
TABLE 301.2.1.3
WIND SPEED CONVERSIONSa
V ult | 110 | 115 | 120 | 130 | 140 | 150 | 160 | 170 | 180 | 190 | 200 |
V asd | 85 | 89 | 93 | 101 | 108 | 116 | 124 | 132 | 139 | 147 | 155 |
For SI: 1 mile per hour = 0.447 m/s.
TABLE 301.2(1)
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
GROUND SNOW LOADo | WIND DESIGN Speedd(mph) | SEISMIC DESIGN CATEGORY | SUBJECT TO DAMAGE FROM | WINTER DESIGN TEMP.e | ICE BARRIER UNDERLAYMENT REQUIREDh | FLOOD HAZARDS g | AIR FREEZING INDEXi | MEAN ANNUAL TEMPj | ||
Weatheringa | Frost line depthb | Termitec | ||||||||
115 | severe | Moderate to heavy | Yes | |||||||
MANUAL J DESIGN CRITERIAn | ||||||||||
Deleted portion of table - owners shall use manual J when required by this code |
For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.
STATION | HEATING DEGREE DAYS (Yearly Total) | DESIGN TEMPERATURES | DEGREES NORTH LATITUDE |
Akron-Canton | 6,037 | 6° | 41-00'- 40-50' |
Cincinnati | 4,410 | 6° | 39-10' |
Cleveland | 6,351 | 5° | 41-30' |
Columbus | 5,660 | 5° | 40-00' |
Dayton | 5,622 | 4° | 39-50' |
Mansfield | 6,403 | 5° | 40-50' |
Sandusky | 5,796 | 6° | 41-30' |
Toledo | 6,494 | 1° | 41-40' |
Youngstown | 6,417 | 4° | 41-10' |
Deviations from the tabulated temperatures shall be permitted to reflect local climates or local weather experience as documented by the building official.
TABLE 301.2(2)
COMPONENT AND CLADDING LOADS FOR A BUILDING WITH A MEAN ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE B (ASD) (psf)a,b,c,d,e
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa.
TABLE 301.2(3)
HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS FOR TABLE 301.2(2)
MEAN ROOF HEIGHT | EXPOSURE | ||
B | C | D | |
15 | 1.00 | 1.21 | 1.47 |
20 | 1.00 | 1.29 | 1.55 |
25 | 1.00 | 1.35 | 1.61 |
30 | 1.00 | 1.40 | 1.66 |
35 | 1.05 | 1.45 | 1.70 |
40 | 1.09 | 1.49 | 1.74 |
45 | 1.12 | 1.53 | 1.78 |
50 | 1.16 | 1.56 | 1.81 |
55 | 1.19 | 1.59 | 1.84 |
60 | 1.22 | 1.62 | 1.87 |
For SI: °C = [(°F)-32]/ 1.8.
FIGURE 301.2(1)
ISOLINES OF THE 971/2 -PERCENT WINTER (DECEMBER, JANUARY AND FEBRUARY) DESIGN TEMPERATURES (°F)
FIGURE 301.2(2)
SEISMIC DESIGN CATEGORIES
D E L E T E D portion of Figure 301.2(2) for Alaska, Hawaii, Puerto Rico and western U.S
FIGURE 301.2(3)
ALTERNATE SEISMIC DESIGN CATEGORIES
D E L E T E D portion of Figure 301.2(3) for Alaska, Hawaii, Puerto Rico and western U.S
FIGURE 301.2(4)
WEATHERING PROBABILITY MAP FOR CONCRETEa,b
FIGURE 301.2(5) A
ULTIMATE DESIGN WIND SPEEDS
D E L E T E D Figure 301.2(5) B Regions where wind design is required
D E L E T E D portion of Figure 301.2(6) for western U.S
For SI: 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 mile = 1.61 km.
FIGURE 301.2(6)
GROUND SNOW LOADS, Pg, (lb/ft) FOR THE EASTERN UNITED STATES
Note: Lines defining areas are approximate only. Local conditions may be more or less severe than indicated by the region classification
FIGURE 301.2(7)
TERMITE INFESTATION PROBABILITY MAP
For SI: 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
Note: a = 4 feet in all cases.
FIGURE 301.2(8)
COMPONENT AND CLADDING PRESSURE ZONES
TABLE 301.2.1.5.1
ULTIMATE DESIGN WIND SPEED MODIFICATION FOR TOPOGRAPHIC WIND EFFECTa,b
Deleted
Deleted
FIGURE 301.2.1.5.1(1)
TOPOGRAPHIC FEATURES FOR WIND SPEED-UP EFFECT
Deleted
FIGURE 301.2.1.5.1(2)
ILLUSTRATION OF WHERE ON A TOPOGRAPHIC FEATURE, WIND SPEED INCREASE IS APPLIED
Deleted
FIGURE 301.2.1.5.1(3)
UPWIND OBSTRUCTION
Components of buildings not required to be designed to resist seismic loads shall be constructed in accordance with the provisions of this code.
TABLE 301.2.2.1.1
SEISMIC DESIGN CATEGORY DETERMINATION
CALCULATED SDS | SEISMIC DESIGN CATEGORY |
SDS<= 0.17 g | A |
0.17 g < SDS<= 0.33 g | B |
0.33 g < SDS<= 0.50 g | C |
Exceptions:
Exception: Detached one-, two- and three-family dwellings in Seismic Design Category C with exterior above-grade concrete walls are allowed to comply with the requirements of Section 608.
Exception: For wood light-frame construction, floors with cantilevers or setbacks not exceeding four times the nominal depth of the wood floor joists are permitted to support braced wall panels that are out of plane with braced wall panels below provided that all of the following are satisfied:
Exception: Portions of floors that do not support shear walls, braced wall panels above, or roofs shall be permitted to extend not more than 6 feet (1829 mm) beyond a shear wall or braced wall line.
Exception: For wood light-frame wall construction, one end of a braced wall panel shall be permitted to extend more than 1 foot (305 mm) over an opening not more than 8 feet (2438 mm) in width in the wall below provided that the opening includes a header in accordance with all of the following:
Exceptions:
Exceptions: Fireplaces, chimneys and masonry veneer in accordance with this code.
Exception: An additional 8 feet (2438 mm) of bearing wall clear height is permitted for gable end walls.
Individual walls or wall studs shall be permitted to exceed these limits as permitted by Chapter 6 provisions, provided that story heights are not exceeded. An engineered design shall be provided for the wall or wall framing members where the limits of Chapter 6 are exceeded. Where the story height limits of this section are exceeded, the design of the building, or the noncompliant portions thereof, to resist wind and seismic loads shall be in accordance with the Ohio building code.
TABLE 301.5
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS (in pounds per square foot)
USE | LIVE LOAD |
Uninhabitable attics without storageb | 10 |
Uninhabitable attics with limited storageb,g | 20 |
Habitable attics and attics served with fixed stairs | 30 |
Balconies (exterior) and deckse | 40 |
Fire escapes | 40 |
Guards and handrailsd | 200h |
Guard in-fill componentsf | 50h |
Passenger vehicle garagesa | 50a |
Rooms other than sleeping rooms | 40 |
Sleeping rooms | 30 |
Stairs | 40c |
For SI: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N.
The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
TABLE 301.6
MINIMUM ROOF LIVE LOADS IN POUNDS-FORCE PER
SQUARE FOOT OF HORIZONTAL PROJECTION
ROOF SLOPE | TRIBUTARY LOADED AREA IN SQUARE FEET FOR ANY STRUCTURAL MEMBER | ||
0 to 200 | 201 to 600 | Over 600 | |
Flat or rise less than 4 inches per foot (1:3) | 20 | 16 | 12 |
Rise 4 inches per foot (1:3) to less than 12 inches per foot (1:1) | 16 | 14 | 12 |
Rise 12 inches per foot (1:1) and greater | 12 | 12 | 12 |
For SI: 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa, 1 inch per foot = 83.3 mm/m.
TABLE 301.7
ALLOWABLE DEFLECTION OF STRUCTURAL MEMBERSb,c
STRUCTURAL MEMBER | ALLOWABLE DEFLECTION |
Rafters having slopes greater than 3:12 with finished ceiling not attached to rafters | L/180 |
Interior walls and partitions | H/180 |
Floors | L/360 |
Ceilings with brittle finishes (including plaster and stucco) | L/360 |
Ceilings with flexible finishes (including gypsum board) | L/240 |
All other structural members | L/240 |
Exterior walls-wind loadsawith plaster or stucco finish | H/360 |
Exterior walls-wind loadsawith other brittle finishes | H/240 |
Exterior walls-wind loadsawith flexible finishes | H/120d |
Lintels supporting masonry veneer wallse | L/600 |
Note:L = span length, H = span height.
FIRE-RESISTANT CONSTRUCTION
Exceptions:
Where referenced in this code, an unoccupied space on an adjoining property may be included in the required fire separation distance, provided that the adjoining property is dedicated or deeded so as to preclude, for the life of the structure, the erection of any building or structure on such space (see section 3781.02 of the Revised Code).
TABLE 302.1(1)
EXTERIOR WALLS
EXTERIOR WALL ELEMENT | MINIMUM FIRE-RESISTANCE RATING | MINIMUM FIRE SEPARATION DISTANCE | |
Walls | Fire-resistance rated | 1 hour-tested in accordance with ASTM E119, UL 263 or Section 703.3 of the Ohio building code with exposure from both sides | 0 feet |
Not fire-resistance rated | 0 hours | >=5 feet | |
Projections | Not allowed | N/A | < 2 feet |
Fire-resistance rated | 1 hour on the underside, or heavy timber, or fire- retardant-treated wooda,b | >=2 feet to < 5 feet | |
Not fire-resistance rated | 0 hours | >=5 feet | |
Openings in walls | Not allowed | N/A | < 3 feet |
25% maximum of wall area | 0 hours | 3 feet | |
Unlimited | 0 hours | 5 feet | |
Penetrations | All | Comply with Section 302.4 | < 3 feet |
None required | 3 feet |
For SI: 1 foot = 304.8 mm. N/A = Not Applicable.
TABLE 302.1(2)
EXTERIOR WALLS-DWELLINGS WITH FIRE SPRINKLERS
EXTERIOR WALL ELEMENT | MINIMUM FIRE-RESISTANCE RATING | MINIMUM FIRE SEPARATION DISTANCE | |
Walls | Fire-resistance rated | 1 hour-tested in accordance with ASTM E119, UL 263 or Section 703.3 of the Ohio building code with exposure from the outside | 0 feet |
Not fire-resistance rated | 0 hours | 3 feeta | |
Projections | Not allowed | N/A | < 2 feet |
Fire-resistance rated | 1 hour on the underside, or heavy timber, or fire- retardant-treated woodb,c | 2 feeta | |
Not fire-resistance rated | 0 hours | 3 feet | |
Openings in walls | Not allowed | N/A | < 3 feet |
Unlimited | 0 hours | 3 feeta | |
Penetrations | All | Comply with Section 302.4 | < 3 feet |
None required | 3 feeta |
For SI: 1 foot = 304.8 mm. N/A = Not Applicable.
Alternatively, each grouping of two dwelling units shall be separated from an adjacent dwelling unit or an adjacent grouping of two dwelling units by a common wall assembly having a fire resistance rating of not less than two hours when tested in accordance with ASTM E119 or UL 263 and/or a floor ceiling assembly having a fire resistance rating of two hours when tested in accordance with ASTM E119 or UL 263. This option is only permissible if the common wall does not contain plumbing or mechanical equipment, ducts or vents in the cavity of the common wall. The common wall shall be rated for fire exposure from both sides and shall extend to and be tight against exterior walls and the underside of the roof sheathing. Penetrations of electrical outlet boxes shall be in accordance with Section 302.4.
Additionally, within any grouping of two dwelling units, separated as indicated above, the individual dwelling units shall be separated vertically and horizontally from adjacent dwelling units by wall and/or floor assemblies having a fire resistance rating of not less than one hour when tested in accordance with ASTM E119 or UL 263.
When assemblies are required to be fire-resistance-rated, the supporting construction of such assemblies shall have an equal or greater fire-resistive rating.
Exception: A parapet is not required in the preceding two cases where the roof covering complies with a minimum Class C rating as tested in accordance with ASTM E108 or UL 790 and the roof decking or sheathing is of noncombustible materials or fire-retardant-treated wood for a distance of 4 feet (1219 mm) on each side of the wall or walls, or one layer of5/8 inch ( 15.9 mm) Type X gypsum board is installed directly beneath the roof decking or sheathing, supported by not less than nominal 2-inch (51 mm) ledgers attached to the sides of the roof framing members, for a distance of not less than 4 feet (1219 mm) on each side of the wall or walls and any openings or penetrations in the roof are not within 4 feet (1219 mm) of the common walls. Fire-retardant-treated wood shall meet the requirements of Sections 802.1.5 and 803.2.1.2.
Exceptions:
Exceptions:
Exception: Where the penetrating items are steel, ferrous or copper pipes, tubes or conduits, the annular space shall be protected as follows:
Exceptions:
TABLE 302.6
DWELLING-GARAGE SEPARATION 1
SEPARATION | MATERIAL |
From the residence and attics | Not less than1/2 -inch gypsum board or equivalent applied to the garage side |
From habitable rooms above the garage | Not less than5/8 -inch Type X gypsum board or equivalent |
Structure(s) supporting floor/ceiling assemblies used for separation required by this section | Not less than1/2 -inch gypsum board or equivalent |
Garages located less than 3 feet from a dwelling unit on the same lot | Not less than1/2 -inch gypsum board or equivalent applied to the interior side of exterior walls that are within this area |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Exception: Flame spread index requirements for finishes shall not apply to trim defined as picture molds, chair rails, baseboards and handrails; to doors and windows or their frames; or to materials that are less than 1/28 -inch ( 0.91 mm) in thickness cemented to the surface of walls or ceilings if these materials exhibit flame spread index values not greater than those of paper of this thickness cemented to a noncombustible backing.
The interior finish shall comply with the following:
Exceptions:
Exception: Cellulosic fiber loose-fill insulation shall not be required to be tested in accordance with CAN/ ULC S 102.2, provided that such insulation complies with the requirements of Sections 302.10.1 and 302.10.3.
Fireblocking shall be provided in wood-framed construction in the following locations:
Exceptions:
Exception: Where heat-producing devices are listed for lesser clearances, combustible insulation complying with the listing requirements shall be separated in accordance with the conditions stipulated in the listing.
Recessed luminaires installed in the building thermal envelope shall meet the requirements of Section 1102.4.5 of this code.
When this code requires an assembly or component to serve in a fire resistive manner but the assembly or component is not required to be fire resistance rated, equivalent fire resistive values can be derived from section 721 in the "Ohio Building Code" or "Resource A, Guidelines on Fire Ratings of Archaic Materials and Assemblies in the International Existing Building Code."
LIGHT, VENTILATION AND HEATING
Exceptions:
Exception: Openings required for light or ventilation shall be permitted to open into a sunroom with thermal isolation or a patio cover, provided that there is an openable area between the adjoining room and the sunroom or patio cover of not less than one-tenth of the floor area of the interior room and not less than 20 square feet (2 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated.
Exception: The glazed areas shall not be required where artificial light and a local exhaust system are provided. The minimum local exhaust rates shall be determined in accordance with Section 1505. Exhaust air from the space shall be exhausted directly to the outdoors.
For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious.
Exceptions:
Exception: A switch is not required where remote, central or automatic control of lighting is provided.
Exceptions:
MINIMUM ROOM AREAS
Exception: Kitchens.
Exception: Kitchens.
CEILING HEIGHT
Exceptions:
Exceptions:
SANITATION
TOILET, BATH AND SHOWER SPACES
For SI: 1 inch = 25.4 mm.
FIGURE 307.1
MINIMUM FIXTURE CLEARANCES
GLAZING
Exceptions:
Exceptions:
Exception: Glazing not in doors or enclosures for hot tubs, whirlpools, saunas, steam rooms, bathtubs and showers shall be permitted to be tested in accordance with ANSI Z 97.1. Glazing shall comply with the test criteria for Class A unless otherwise indicated in Table 308.3.1(2).
TABLE 308.3.1(1)
MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING CPSC 16 CFR 1201
EXPOSED SURFACE AREA OF ONE SIDE OF ONE LITE | GLAZING IN STORM OR COMBINATION DOORS (Category Class) | GLAZING IN DOORS (Category Class) | GLAZED PANELS REGULATED BY SECTION 308.4.3 (Category Class) | GLAZED PANELS REGULATED BY SECTION 308.4.2 (Category Class) | GLAZING IN DOORS AND ENCLOSURES REGULATED BY SECTION 308.4.5 (Category Class) | SLIDING GLASS DOORS PATIO TYPE (Category Class) |
9 square feet or less | I | I | NR | I | II | II |
More than 9 square feet | II | II | II | II | II | II |
For SI: 1 square foot = 0.0929 m2. NR = No Requirement.
TABLE 308.3.1(2)
MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING ANSI Z 97.1
EXPOSED SURFACE AREA OF ONE SIDE OF ONE LITE | GLAZED PANELS REGULATED BY SECTION 308.4.3 (Category Class) | GLAZED PANELS REGULATED BY SECTION 308.4.2 (Category Class) | DOORS AND ENCLOSURES REGULATED BY SECTION 308.4.5a (Category Class) |
9 square feet or less | No requirement | B | A |
More than 9 square feet | A | A | A |
For SI: 1 square foot = 0.0929 m2.
Exceptions:
Exceptions:
Exceptions:
Exception: An attached top rail or handrail is not required where the glass baluster panels are laminated glass with two or more glass plies of equal thickness and of the same glass type.
Exception: Glazing that is more than 60 inches (1524 mm), measured horizontally and in a straight line, from the water's edge of a bathtub, hot tub, spa, whirlpool or swimming pool or from the edge of a shower, sauna or steam room.
Exceptions:
The rail shall be capable of withstanding a horizontal load of 50 pounds per linear foot (730 N/m) without contacting the glass and have a cross-sectional height of not less than 11/2 inches (38 mm).
Exception: Where the glazing is protected by a guard complying with Section 312 and the plane of the glass is more than 18 inches (457 mm) from the guard.
For SI: 1 inch = 25.4 mm.
FIGURE 308.4.7
HAZARDOUS GLAZING LOCATIONS AT BOTTOM STAIR LANDINGS
SKYLIGHT, UNIT.
SKYLIGHTS AND SLOPED GLAZING.
TUBULAR DAYLIGHTING DEVICE (TDD).
Structural wind load design pressures for glass-glazed unit skylights different than the size tested in accordance with Section 308.6.9 shall be permitted to be different than the design value of the tested unit where determined in accordance with one of the following comparative analysis methods:
GARAGES AND CARPORTS
The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway.
The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway. Exception: Asphalt surfaces shall be permitted at ground level in carports.
EMERGENCY ESCAPE AND RESCUE OPENINGS
Exceptions: Where the dwelling or dwelling unit is equipped with an automatic sprinkler system installed in accordance with Section 2904, sleeping rooms in basements shall not be required to have emergency escape and rescue openings provided that the basement has one of the following:
Exception: Grade floor openings or below-grade openings shall have a net clear opening area of not less than 5 square feet ( 0.465 m2).
Exception: The ladder or steps required by Section 310.2.3.1 shall be permitted to encroach not more than 6 inches (152 mm) into the required dimensions of the window well.
Exception: A drainage system for window wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, as detailed in Table 405.1.
Emergency escape and rescue openings installed under decks and porches shall be fully openable and provide a path not less than 36 inches (914 mm) in height to a yard or court.
Exception: Replacement windows installed in accordance with Section 113.5.1 shall not be required to comply with 310.2.1
Exception: A drainage system for area wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, as detailed in Table 405.1.
Exception: N ew sleeping rooms created in an existing basement shall be provided with emergency escape and rescue openings in accordance with Section 310.1.
MEANS OF EGRESS
Exception: Exterior balconies less than 60 square feet ( 5.6 m2) and only accessed from a door are permitted to have a landing that is less than 36 inches (914 mm) measured in the direction of travel.
Exception: The landing or floor on the exterior side shall be not more than 8 1/4 -inches (209 mm) below the top of the threshold provided that the door does not swing over the landing or floor.
Where exterior landings or floors serving the required egress door are not at grade, they shall be provided with access to grade by means of a ramp in accordance with Section 311.8 or a stairway in accordance with Section 311.7.
Exception: A top landing is not required for the stairway located on the exterior side of the door, provided that the threshold of the door is not more than 30" above the adjacent grade and the door does not swing over the stairway.
Exception: The width of spiral stairways shall be in accordance with Section 311.7.10.1.
Exceptions:
Exceptions:
Exception: The tread depth at spiral stairways shall be in accordance with Section 311.7.10.1.
Exception: A nosing projection is not required where the tread depth is not less than 11 inches (279 mm).
Exception: A floor or landing is not required at the top of an interior flight of stairs, including stairs in an enclosed garage, provided that a door does not swing over the stairs.
Exceptions:
Exception: Where nosings of landings, floors or passing flights project into the stairway reducing the clearance at passing handrails, handrails shall project not more than 61/2 inches (165 mm) into the stairway, provided that the stair width and handrail clearance are not reduced to less than that required.
Exceptions:
Exception: Alternating tread devices are allowed to be used as an element of a means of egress for lofts, mezzanines and similar areas of 200 gross square feet ( 18.6 m2) or less where such devices do not provide exclusive access to a kitchen or bathroom.
Exception: Ships ladders are allowed to be used as an element of a means of egress for lofts, mezzanines and similar areas of 200 gross square feet ( 18.6 m2) or less that do not provide exclusive access to a kitchen or bathroom.
GUARDS AND WINDOW FALL PROTECTION
Exception: Guards are not required where a protective bar is installed 34 inches to 38 inches (864 mm to 965 mm) above the porch or deck on the interior side of the screening. The protective bar shall be capable of resisting a horizontal load of 50 pounds per lineal foot (730 N/m) without contacting the screen and be a minimum of 11/2 inches (38 mm) in height.
Exceptions:
Exceptions:
AUTOMATIC FIRE SPRINKLER SYSTEMS
SMOKE ALARMS
Exception: A system meeting the requirements of Section 314.7 is not required to include both technologies.
Exceptions:
Exception: Interconnection of smoke alarms in existing areas shall not be required where the alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for interconnection without the removal of interior finishes.
Exceptions:
Exception. Where separate smoke alarms are provided meeting all other requirements of this section, the fire alarm system is not required to be a permanent fixture of the occupancy or owned by the homeowner.
CARBON MONOXIDE ALARMS
Exception. Where separate carbon monoxide alarms are provided meeting all other requirements of this section, the carbon monoxide detection system is not required to be a permanent fixture of the occupancy or owned by the homeowner.
FOAM PLASTIC
Exception: Foam plastic insulation more than 4 inches (102 mm) thick shall have a flame spread index of not more than 75 and a smoke-developed index of not more than 450 where tested at a thickness of not more than 4 inches (102 mm), provided that the end use is approved in accordance with Section 316.6 using the thickness and density intended for use.
The ignition barrier is not required where the foam plastic insulation has been tested in accordance with Section 316.6.
PROTECTION OF WOOD AND WOOD-BASED PRODUCTS
AGAINST DECAY
Exceptions:
Exception: Quality marks on lumber less than 1 inch (25 mm) nominal thickness, or lumber less than nominal 1 inch by 5 inches (25 mm by 127 mm) or 2 inches by 4 inches (51 mm by 102 mm) or lumber 36 inches (914 mm) or less in length shall be applied by stamping the faces of exterior pieces or by end labeling not less than 25 percent of the pieces of a bundled unit.
Exceptions:
PROTECTION AGAINST SUBTERRANEAN TERMITES
Exceptions:
SITE ADDRESS
ACCESSIBILITY
In structures with 1, 2 or 3 dwelling units, the accessibility provisions of this code are not required but when non-required accessibility components are intended to be installed inside the dwellings, they shall comply with the provisions for Type A, Type B, Type C (Visitable), or Accessible units in ICC/ANSI A 117.1 listed in Chapter 44 to the extent of the installation.
Exception: Owner-occupied lodging houses with five or fewer guestrooms constructed in accordance with the Residential Code of Ohio are not required to be accessible.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 320.4.
When this code applies to structures of four or more dwellings and Type B units are required, the common and public use areas serving the Type B dwellings and the accessible route connecting the common and public use areas to the Type B units shall comply with ICC/ANSI A 117.1 listed in Chapter 44.
Exception:
If due to circumstances outside the control of the owner, either the slope of the finished ground level between accessible facilities and buildings exceeds one unit vertical in 12 units horizontal (1:12), or where physical barriers or legal restrictions prevent the installation of an accessible route, a vehicular route with parking that complies with ICC/ANSI A 117.1 listed in Chapter 44 at each public or common use facility or building is permitted in place of the accessible route.
Where no such arrival points are within 50 feet (15 240 mm) of the entrance, the closest arrival point shall be used unless that arrival point serves the story required by Section 320.4.1.1.
For purposes of applying section 320, multistory units are dwellings with finished, habitable space on more than one level of the unit.
Where no such arrival points are within 50 feet ( 15.24 m) of the primary entrances, the closest arrival points shall be used.
ELEVATORS AND PLATFORM LIFTS
FLOOD-RESISTANT CONSTRUCTION
Electrical systems, equipment and components; heating, ventilating, air-conditioning; plumbing appliances and plumbing fixtures; duct systems; and other service equipment shall be located at or above the elevation required in Section 322.2 or 322.3. If replaced as part of a substantial improvement, electrical systems, equipment and components; heating, ventilating, air-conditioning and plumbing appliances and plumbing fixtures; duct systems; and other service equipment shall meet the requirements of this section. Systems, fixtures, and equipment and components shall not be mounted on or penetrate through walls intended to break away under flood loads.
Exception: Locating electrical systems, equipment and components; heating, ventilating, air-conditioning; plumbing appliances and plumbing fixtures; duct systems; and other service equipment is permitted below the elevation required in Section 322.2 or 322.3 provided that they are designed and installed to prevent water from entering or accumulating within the components and to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the design flood elevation in accordance with ASCE 24. Electrical wiring systems are permitted to be located below the required elevation provided that they conform to the provisions of the electrical part of this code for wet locations.
Exception: Enclosed areas below the design flood elevation, including basements with floors that are not below grade on all sides, shall meet the requirements of Section 322.2.2.
Exception: Unless designed in accordance with Section 404:
For the purpose of this exception, unsupported height is the distance from the finished grade of the under-floor space to the top of the wall.
Exception: In Coastal A Zones, stem wall foundations supporting a floor system above and backfilled with soil or gravel to the underside of the floor system shall be permitted provided that the foundations are designed to account for wave action, debris impact, erosion and local scour. Where soils are susceptible to erosion and local scour, stem wall foundations shall have deep footings to account for the loss of soil.
Areas below stairways and ramps shall not be enclosed with walls below the design flood elevation unless such walls are constructed in accordance with Section 322.3.5.
STORM SHELTERS
SOLAR ENERGY SYSTEMS
Exceptions:
MEZZANINES
- Deleted
SWIMMING POOLS, SPAS AND HOT TUBS
- Deleted
STATIONARY STORAGE BATTERY SYSTEMS
Exceptions:
POST FRAME ACCESSORY STRUCTURES
Post and frame structures and portions thereof outside the above structural limitations of this standard shall be accompanied by structural calculations as required by the residential building official or designed under the provisions of section 106.5 of the Residential Code of Ohio (RCO). Post and frame structures shall comply with the structural design requirements of section 301 of the RCO.
TABLE 328.3
POST FRAME PIER FOOTING DIAMETERS1,2,3,4
Building width (length of truss) including overhang (feet) | ||||
24 | 28 | 32 | 36 | |
Diameter (inches) 20# roof snow load | 18 | 20 | 22 | 22 |
Diameter (inches) 30# roof snow load | 18 | 22 | 24 | 26 |
FIGURE 328
POST AND FRAME WALL SECTION.
(NO SCALE)
FIGURE 328.1
POST UPLIFT PROTECTION EXCEPTION
(NO SCALE)
Exceptions:
TABLE 328.4.5
GABLE END HEADER SIZES.
Opening Width (feet) | 10 | 12 | 16 |
Header Size (inches) | 2-2x8 | 2-2x10 | 2-2x12 |
TABLE 328.4.7
BEAM OR TRUSS CONNECTION AT POSTS
MINIMUM FASTENERS OR TOTAL SHEAR OR WITHDRAW VALUESa,b,c
Building Width (Length of Truss) including overhang (feet) | ||||
24 | 28 | 32 | 36 | |
Shear or withdraw (pounds) 20 lb snow load | 3360 | 3920 | 4480 | 5040 |
Number of Bolts, 20 lb roof snow load | 2 | 2 | 2 | 3 |
Shear or withdraw (pounds) 30 lb roof snow load | 4320 | 5040 | 5760 | 6480 |
Number of Bolts, 30 lb roof snow load | 2 | 3 | 3 | 3 |
TABLE 328.6
KNEE BRACE VERTICAL DISTANCE.
Wall Height | Vertical Dimension |
8'-0" and 9'-0" | 1'-6" |
10'-0" and 11'-0" | 2'-0" |
12'-0" and 13'-0" | 3'-0" |
14'-0" through 16'-0" | 4'-0" |
TABLE 328.7
STRUCTURAL FASTENERS
Fastener Schedule for Structural Members | ||
Description of Building Element | Number and Type of Fastener | Attachment type |
Uplift blocking to post | 5-16d Hot Dipped Galvanized | Each block |
Skirt board to post | 2-16d Hot Dipped Galvanized | Face nail |
Wall girt to post | 2-16d Hot Dipped Galvanized | Face nail |
Diagonal cross bracing to post | 2-16d Hot Dipped Galvanized | Face nail |
Diagonal cross bracing to skirt board | 2-10d Hot Dipped Galvanized | Face nail |
Diagonal cross bracing to wall girts, beam, or header | 2-10d | Face nail |
Knee brace to post | 3-16d Hot Dipped Galvanized | Face nail |
Knee brace to top chord of truss or rafter | 3-10d | Face nail |
Knee brace to bottom chord of truss or ceiling joist | 3-10d | Face nail |
Roof purlin to truss or rafter with span of 2' or 4' | 2-16d | Face nail |
Roof purlin to truss or rafter with span of 8' | Mechanical fastener with uplift protection greater than 225 pounds. | Per manufacturer installation manual |
Replaces: 4101:8-3-01
Ohio Admin. Code 4101:8-3-01
Five Year Review (FYR) Dates: 07/01/2024
Promulgated Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule Amplifies: 3781.01, 4740.14, 3791.04, 3781.11, 3781.10, 3781.06
Prior Effective Dates: 05/27/2006, 01/01/2013, 07/01/2014, 01/01/2016