Owners and operators should carefully review the release detection requirements described in paragraphs (B) and (C) of this rule in order to determine which of the following methods apply to their UST system.
Nominal Tank Capacity | Minimum Duration of Test | Weekly Standard (One Test) | Monthly Standard (Four Test Average) |
550 gallons or less | 36 hours | 10 gallons | 5 gallons |
551-1,000 gallons (when tank diameter is 64 inches) | 44 hours | 9 gallons | 4 gallons |
551-1,000 gallons (when tank diameter is 48 inches) | 58 hours | 12 gallons | 6 gallons |
551-1,000 gallons (requires tank tightness test every five years) | 36 hours | 13 gallons | 7 gallons |
1,001-2,000 gallons (requires tank tightness test every five years) | 36 hours | 26 gallons | 13 gallons |
Owners and operators should carefully review the release detection requirements described in paragraphs (B) and (C) of this rule in order to determine which of the following methods apply to their UST system.
Owners and operators should carefully review the release detection requirements described in paragraphs (B) and (C) of this rule in order to determine which of the following methods apply to their UST system.
UST system owners and operators shall maintain records demonstrating compliance with this chapter, and these records shall be maintained pursuant to the following: