N.D. Admin. Code 69-09-02-27

Current through Supplement No. 393, July, 2024
Section 69-09-02-27 - Determination of average meter error

Whenever a metering installation is found upon any test to be in error by more than two percent at any test load, the average error shall be determined as follows:

1. If the metering installation is used to measure a load which has practically constant characteristics, such as a streetlighting load, the meter shall be tested under similar conditions of load and the accuracy of the meter "as found" shall be considered as the average error.
2. If a single-phase, or direct current, metering installation is used on a varying load, the average error shall be the weighted algebraic average of the error at light load, with a weighting of one, and the error at heavy load, with a weighting of four.
3. If a polyphase metering installation is used on a varying load, the average error shall be the weighted algebraic average of the error at light load (unity power factor) with a weighting of one, the error at heavy load (unity power factor) with a weighting of four, and the error at heavy load (fifty percent lagging power factor) with a weighting of two.

N.D. Admin Code 69-09-02-27

General Authority: NDCC 49-02-11

Law Implemented: NDCC 49-02-11