Section 62-04-06-04 - Receptors or sumps1.Installation. Waste receptors or sumps serving indirect waste pipes shall not be installed in any toilet room, nor in any inaccessible or unventilated space such as a closet or storeroom. 2.Location. The receptor must be located so that the required airgap between the indirect waste line and receptor can be maintained under all conditions of backflow. If this is not possible then the receptor at such a location must be a sewer ejector installed as required under section 62-03-11-07 and the discharge must be indirectly connected to the building drainage system as required by subsection 1 of section 62-03-09-01. 3.Strainers and baskets. Every indirect waste receptor shall be equipped with a readily removable metal basket over which all indirect waste pipes shall discharge, or the indirect waste receptor outlet shall be equipped with a beehive strainer not less than four inches [10.16 centimeters] in height. 4.Splashing to be prevented. All plumbing receptors receiving the discharge of the indirect waste pipes shall be of such shape and capacity as to prevent splashing or flooding. 5.Domestic or culinary fixtures prohibited as receptors. No plumbing fixture which is used for domestic or culinary purposes shall be used to receive the discharge of an indirect waste except that in a residence a laundry tray may be used as a receptor for a water conditioning unit. General Authority: NDCC 43-18.1-03
Law Implemented: NDCC 43-18.1-04
N.D. Admin Code 62-04-06-04