N.D. Admin. Code 33-24-05-664

Current through Supplement No. 393, July, 2024
Section 33-24-05-664 - Used oil storage

Used oil burners are subject to all applicable spill prevention, control, and countermeasures [40 CFR part 112] in addition to the requirements of sections 33-24-05-660 through 33-24-05-669. Used oil burners are also subject to the underground storage tank ( 33-24-08) standards for used oil stored in underground tanks whether or not the used oil exhibits any characteristics of hazardous waste, in addition to the requirements of sections 33-24-05-660 through 33-24-05-669.

1.Storage units. Used oil burners may not store used oil in units other than tanks, containers, or units subject to regulation under sections 33-24-05-01 through 33-24-05-190, 33-24-05-300 through 33-24-05-524, 33-24-05-550 through 33-24-05-559, 33-24-05-800 through 33-24-05-819, or the applicable requirements of subsection 5 of section 33-24-06-16.
2.Condition of units. Containers and aboveground tanks used to store oil at burner facilities must be:
a. In good condition (no severe rusting, apparent structural defects, or deterioration); and
b. Not leaking (no visible leaks).
3.Secondary containment for containers. Containers used to store used oil at burner facilities must be equipped with a secondary containment system.
a. The secondary containment system must consist of, at a minimum:
(1) Dikes, berms, or retaining walls; and
(2) A floor. The floor must cover the entire area within the dike, berm, or retaining wall.
b. The entire containment system, including walls and floor, must be sufficiently impervious to used oil to prevent any used oil released into the containment system from migrating out of the system to the soil, ground water, or surface water.
4.Secondary containment for existing aboveground tanks. Existing aboveground tanks used to store used oil at burner facilities must be equipped with a secondary containment system.
a. The secondary containment system must consist of, at a minimum:
(1) Dikes, berms, or retaining walls; and
(2) A floor. The floor must cover the entire area within the dike, berm, or retaining wall except areas where existing portions of the tank meet the ground; or
(3) An equivalent secondary containment system.
b. The entire containment system, including walls and floor, must be sufficiently impervious to used oil to prevent any used oil released into the containment system from migrating out of the system to the soil, ground water, or surface water.
5.Secondary containment for new aboveground tanks. New aboveground tanks used to store used oil at burner facilities must be equipped with a secondary containment system.
a. The secondary containment system must consist of, at a minimum:
(1) Dikes, berms, or retaining walls; and
(2) A floor. The floor must cover the entire area within the dike, berm, or retaining wall; or
(3) An equivalent secondary containment system.
b. The entire containment system, including walls and floor, must be sufficiently impervious to used oil to prevent any used oil released into the containment system from migrating out of the system to the soil, ground water, or surface water.
6.Labels.
a. Containers and aboveground tanks used to store used oil at burner facilities must be labeled or marked clearly with the words "Used Oil".
b. Fill pipes used to transfer used oil into underground storage tanks at burner facilities must be labeled or marked clearly with the words "Used Oil".
7.Response to releases. Upon detection of a release of used oil to the environment not subject to the requirements of 33-24-08, sections 33-24-08-50 through 33-24-08-59, a burner must perform the following cleanup steps:
a. Stop the release;
b. Contain the released used oil;
c. Clean up and manage properly the released used oil and other materials; and
d. If necessary, repair or replace any leaking used oil storage containers or tanks prior to returning them to service.

N.D. Admin Code 33-24-05-664

Effective January 1, 1994; amended effective July 1, 1997; December 1, 2003.
Amended by Administrative Rules Supplement 2016-359, January 2016, effective 1/1/2016.

General Authority: NDCC 23-20.3-03

Law Implemented: NDCC 23-20.3-03, 23-20.3-04