625.41 Overcurrent protection. Overcurrent protection for feeders and branch circuits supplying vehicle charging equipment must be sized for continuous duty and must have a rating of not less than one hundred twenty-five percent of the maximum load of the equipment. For these installations, "maximum load of equipment" means the setting the electrician adjusted the device to. The adjustment may not be readily accessible or cannot easily be adjusted by the consumer. The electrician shall label the device if set to a value less than the maximum nameplate rating. The contractor shall assure the size of the service feeding these devices is adequate.
N.D. Admin Code 24.1-06-06-25
General Authority: NDCC 43-09-05
Law Implemented: NDCC 43-09-21, 43-09-22