15A N.C. Admin. Code 18C.0801

Current through Register Vol. 39, No. 9, November 1, 2024
Section 18C .0801 - CAPACITIES: DETERMINING MINIMUM EFFECTIVE VOLUME

The minimum effective volume of pressure tanks, in gallons, shall equal the peak demand, in gallons per minute, minus the pumping capacity (gpm), multiplied by 20.

15A N.C. Admin. Code 18C .0801

Authority G.S. 130A-315; 130A-317; P.L. 93-523;
Eff. January 1, 1977;
Readopted Eff. December 5, 1977;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. November 23, 2015.
Authority G.S. 130A-315; 130A-317; P.L. 93-523;
Eff. 1/1/1977;
Readopted Eff. 12/5/1977.