15A N.C. Admin. Code 2T.0706

Current through Register Vol. 39, No. 13, January 2, 2025
Section 02T .0706 - SETBACKS
(a) The setbacks for infiltration sites shall be as follows:

Spray (feet)

Drip (feet)

Basin (feet)

Each habitable residence or place of assembly under separate ownership or not to be maintained as part of the project site

400

100

100

Each habitable residence or place of assembly owned by the permittee to be maintained as part of the project site

200

15

50

Each private or public water supply source

100

100

100

Surface waters such as intermittent and perennial streams, perennial waterbodies, and wetlands

200

200

200

Groundwater lowering ditches where the bottom of the ditch intersects the SHWT

200

200

200

Subsurface groundwater lowering drainage systems

200

200

200

Surface water diversions such as ephemeral streams, waterways, and ditches

50

50

50

Each well with exception of monitoring wells

100

100

100

Each property line

150

50

50

Top of slope of embankments or cuts of two feet or more in vertical height

100

100

100

Each water line from a disposal system

10

10

10

Public right of way

50

50

50

Nitrification field

20

20

20

Each building foundation or basement

15

15

15

Impounded public water supplies

500

500

500

Public shallow groundwater supply (less than 50 feet deep)

500

500

500

(b) Setbacks in Paragraph (a) of this Rule to surface waters, groundwater lowering ditches, and subsurface groundwater lowering drainage systems shall be 100 feet if the treatment units are designed to meet effluent limits of 7 mg/L of total nitrogen and 3 mg/L of total phosphorus.
(c) Setbacks in Paragraph (a) of this Rule to surface waters, groundwater lowering ditches, and subsurface groundwater lowering drainage systems shall be 50 feet if the treatment units are designed to meet effluent limits of 4 mg/L of total nitrogen and 2 mg/L of total phosphorus. This setback provision shall not apply to SA waters.
(d) Treatment and storage facilities associated with systems permitted under this Section shall adhere to the setback requirements in Section .0500 of this Subchapter, except as provided in this Rule.
(e) Setback waivers shall be written, notarized, signed by all parties involved, and recorded with the county Register of Deeds. Waivers involving the compliance boundary shall be in accordance with 15A NCAC 02L .0107.
(f) Setbacks to property lines established in Paragraphs (a) and (d) of this Rule shall not be applicable if the permittee, or the entity from which the permittee is leasing, owns both parcels separated by the property line.
(g) Habitable residences or places of assembly under separate ownership constructed after the non-discharge facilities were originally permitted or subsequently modified are exempt from the setback requirements in Paragraphs (a) and (d) of this Rule.

15A N.C. Admin. Code 02T .0706

Authority G.S. 143-215.1; 143-215.3(a);
Eff. September 1, 2006;
Readopted Eff. September 1, 2018.
Authority G.S. 143-215.1; 143-215.3(a);
Eff. 9/1/2006.
Readopted by North Carolina Register Volume 33, Issue 07, October 1, 2018 effective 9/1/2018.