[Note: The North Carolina Board of Examiners for Engineers and Surveyors has determined, via letter dated December 1, 2005, that preparation of engineering design documents pursuant to this Paragraph constitutes practicing engineering under G.S. 89C.]
Storm sewers and other utilities not listed below (vertical) | 18 inches |
Water mains (vertical-water over sewer including in benched trenches) or (horizontal) | 18 inches 10 feet |
Reclaimed water lines (vertical - reclaimed over sewer) or (horizontal) | 18 inches 2 feet |
Any private or public water supply source consisting of wells, WS-I waters, Class I, Class II, or Class III reservoirs used as a source of drinking water | 100 feet |
Waters classified WS-II, WS-III, WS-IV, B, SA, ORW, HQW, or SB from normal high water or tide elevation, wetlands that are directly abutting these waters, and wetlands classified as UWL or SWL | 50 feet |
Any other stream, lake, impoundment, wetlands classified as WL, waters classified as C, SC, or WS-V, or ground water lowering and surface drainage ditches | 10 feet |
Any building foundation | 5 feet |
Any basement | 10 feet |
Top slope of embankment or cuts of 2 feet or more vertical height | 10 feet |
Drainage systems and interceptor drains | 5 feet |
Any swimming pool | 10 feet |
Final earth grade (vertical) | 36 inches |
15A N.C. Admin. Code 02T .0305
Eff. September 1, 2006;
Readopted Eff. September 1, 2018;
Amended Eff. April 1, 2021.
Eff. 9/1/2006.