Current through Register Vol. 46, No. 45, November 2, 2024
Section 225-2.4 - Requirements for owners or operators of facilities proposing to burn waste oilAs part of an application for a permit or registration to burn waste oil, except as provided in subdivision (d) of this Section, owners or operators of facilities must meet the following criteria:
(a) submit an analysis of the waste oil proposed to be burned to the department, pursuant to Section 225-2.6 of this Subpart.(b) a stationary combustion installation or process source that proposes to burn waste oil must have a minimum operating heat input of 20 million Btus per hour or greater.(c) an incinerator that proposes to burn waste oil must have a minimum charging capacity that equals or exceeds 2,000 pounds per hour of refuse.(d) an owner or operator of space heaters located in automotive maintenance/service facilities or marine service facilities may burn waste oil and be excepted from the requirements of this section, where the following conditions are met: (1) the maximum operating heat input is less than 500,000 Btus per hour;(2) the waste oil is generated on site (this includes waste oils generated by do-it-yourself customers that the facility is required to accept) or at another facility under common ownership; and(3) the waste oil meets the criteria in Section 225-2.5 Table 1 of this Subpart, except that lead may not exceed 25 parts per million (ppm) by weight (water free basis) of fuel.N.Y. Comp. Codes R. & Regs. Tit. 6 §§ 225-2.4
Adopted New York State Register March 18, 2020/Volume XLII, Issue 11, eff. 4/2/2020