N.Y. Comp. Codes R. & Regs. tit. 16 § 255.481

Current through Register Vol. 46, No. 41, October 9, 2024
Section 255.481 - Atmospheric corrosion control: monitoring
(a) Each operator must inspect each pipeline or portion of pipeline that is exposed to the atmosphere for evidence of atmospheric corrosion, as follows:

If the pipeline is located:Then the frequency of inspection is:
Onshore Other than a Service Line ....... At least once every 3 calendar years, but with intervals not exceeding 39 months
Onshore Service Line ....... At least once every 5 calendar years, but within intervals not exceeding 63 months
Offshore ....... At least once each calendar year, but with intervals not exceeding 15 months

(b) During inspections the operator must give particular attention to pipe at soil-to-air interfaces, under thermal insulation, under disbonded coatings, at pipe supports, in splash zones, at deck penetrations, and in spans over water.
(c) If atmospheric corrosion is found during an inspection, the operator must provide protection against the corrosion as required by section 255.479 of this Part.

N.Y. Comp. Codes R. & Regs. Tit. 16 § 255.481