N.Y. Comp. Codes R. & Regs. tit. 16 § 255.191

Current through Register Vol. 46, No. 45, November 2, 2024
Section 255.191 - Design pressure of plastic fittings
(a) The design pressure of polyvinyl chloride (PVC) Schedules-40 and 80 thermoplastic fittings must be obtained from the following table:

PVC Type IIClass Location
Size inchesSchedule12 & 3412 & 34
1/240100100100100100100
80100100100100100100
3/44010010096100100100
80100100100100100100
1401001009090100100
80100100100100100100
80100100100100100100
11/4401009274100100100
80100100100100100100
11/2401008386100100100
8010010094100100100
240896955100100100
8010010081100100100
21/240997661100100100
8010010085100100100
340846653100100100
801009475100100100
31/24077604810010096
801008669100100100
44071564410010089
801008165100100100
5408249391009778
80937258100100100
6405644351008871
80897056100100100

Note:

These pressure ratings are the same value as the design pressure of the corresponding pipe size and schedule in the same class location, as determined by the formula given in section 255.121 of this Part.

N.Y. Comp. Codes R. & Regs. Tit. 16 § 255.191

These pressure ratings are the same value as the design pressure of the corresponding pipe size and schedule in the same class location, as determined by the formula given in section 255.121 of this Part and the limitations of section 255.123.