N.Y. Comp. Codes R. & Regs. tit. 16 § 92.11

Current through Register Vol. 46, No. 25, June 18, 2024
Section 92.11 - Meter registers and add-ons, auxiliary devices, and data processing
(a) Meter demand registers shall be tested as specified in the Part 92 Operating Manual.
(b) Meter add-ons, such as pulse initiators, communications modules, etc., shall be verified for performance and effect on the meter as part of the approval process for the meter on which they will be used as specified in Part 93 of this Title. The tests for new meters specified in section 92.7 of this Part and the in-service tests specified in section 92.10 of this Part shall not apply to these add-ons.
(c) Functions performed on the raw meter data by data processing systems shall be verified for compliance with specifications, functionality, and accuracy before use. The approval requirements of Part 93 of this Title, the tests for new meters specified in section 92.7 of this Part and the in-service tests specified in section 92.10 of this Part shall not apply to these functions.
(d) Auxiliary devices, such as pulse recorders, totalizers, etc., must be approved for use in customer billing applications as specified in Part 93 of this Title. Their performance will be verified as part of the approval process. The tests for new meters specified in section 92.7 of this Part and the in-service tests specified in section 92.10 of this Part shall not apply to these devices.

N.Y. Comp. Codes R. & Regs. Tit. 16 § 92.11