N.Y. Comp. Codes R. & Regs. tit. 16, Appendices, app 14-B

Current through Register Vol. 46, No. 45, November 2, 2024
Appendix 14-B

QUALIFICATION OF PIPE

(I) Listed Pipe Specifications. See section 10.3 of this Title for effective edition of each of the listed pipe specifications.

A. Listed Pipe Specifications

API Spec 5L-Steel pipe, "API Specification for Line Pipe"

ASTM A53/A53M-Steel pipe, "Standard Specification for Pipe, Steel Black and Hot-Dipped, Zinc-Coated, Welded and Seamless"

ASTM A106/A106M-Steel pipe, "Standard Specification for Seamless Carbon Steel Pipe for High Temperature Service"

ASTM A333/A333M-Steel pipe, "Standard Specification for Seamless and Welded Steel Pipe for Low Temperature Service"

ASTM A381-Steel pipe, "Standard Specification for Metal-Arc-Welded Steel Pipe for Use with High-Pressure Transmission Systems"

ASTM A671/A671M-Steel pipe, "Standard Specification for Electric-Fusion-Welded Pipe for Atmospheric and Lower Temperatures"

ASTM A672/A672M-Steel pipe, "Standard Specification for Electric-Fusion-Welded Steel Pipe for High-Pressure Service at Moderate Temperatures"

ASTM A691-Steel pipe, "Standard Specification for Carbon and Alloy Steel Pipe, Electric-Fusion-Welded for High Pressure Service at High Temperatures"

ASTM B88-Copper tubing, "Standard Specification for Seamless Copper Water Tube"

ASTM D2513-Thermoplastic pipe and tubing, "Standard Specification for Thermoplastic Gas Pressure Pipe, Tubing, and Fittings"

ASTM D2517-Thermosetting plastic pipe and tubing, "Standard Specification for Reinforced Epoxy Resin Gas Pressure Pipe and Fittings"

ASTM F2785-"Standard Specification for Polyamide 12 Gas Pressure Pipe, Tubing, and Fittings" (PA-12)

ASTM F2817-"Standard Specification for Poly (Vinyl Chloride) (PVC) Gas Pressure Pipe and Fittings for Maintenance or Repair"

ASTM F2945-"Standard Specification for Polyamide 11 Gas Pressure Pipe, Tubing, and Fittings" (PA-11)

B. Other Listed Specifications for Components

ASME B16.40-"Manually Operated Thermoplastic Gas Shutoffs and Valves in Gas Distribution Systems"

ASTM D2513-"Standard Specification for Polyethylene (PE) Gas Pressure Pipe, Tubing, and Fittings"

ASTM D2517-Thermosetting plastic pipe and tubing, "Standard Specification for Reinforced Epoxy Resin Gas Pressure Pipe and Fittings"

ASTM F2785-"Standard Specification for Polyamide 12 Gas Pressure Pipe, Tubing, and Fittings" (PA-12)

ASTM F2945-"Standard Specification for Polyamide 11 Gas Pressure Pipe, Tubing, and Fittings" (PA-11)

ASTM F1055-"Standard Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene Pipe and Tubing"

ASTM F1924-"Standard Specification for Plastic Mechanical Fittings for Use on Outside Diameter Controlled Polyethylene Gas Distribution Pipe and Tubing"

ASTM F1948-12 "Standard Specification for Metallic Mechanical Fittings for Use on Outside Diameter Controlled Thermoplastic Gas Distribution Pipe and Tubing"

ASTM F1973-"Standard Specification for Factory Assembled Anodeless Risers and Transition Fittings in Polyethylene (PE) and Polyamide 11 (PA 11) and Polyamide 12 (PA 12) Fuel Gas Distribution Systems"

ASTM F2600-"Standard Specification for Electrofusion Type Polyamide-11 Fittings for Outside Diameter Controlled Polyamide-11 Pipe and Tubing"

ASTM F2145-"Standard Specification for Polyamide 11 (PA 11) and Polyamide 12 (PA12) Mechanical Fittings for Use on Outside Diameter Controlled Polyamide 11 and Polyamide 12 Pipe and Tubing"

ASTM F2767-"Specification for Electrofusion Type Polyamide- 12 Fittings for Outside Diameter Controlled Polyamide-12 Pipe and Tubing for Gas Distribution"

ASTM F2817-"Standard Specification for Poly (Vinyl Chloride) (PVC) Gas Pressure Pipe and Fittings for Maintenance or Repair"

(II) Steel pipe of unknown or unlisted specification.

(II) (A) Bending properties.

For pipe 2 inches (51 millimeters) or less in diameter, a length of pipe must be cold bent through at least 90 degrees around a cylindrical mandrel that has a diameter 12 times the diameter of the pipe, without developing cracks at any portion and without opening the longitudinal weld.

For pipe more than 2 inches (51 millimeters) in diameter, the pipe must meet the requirements of the flattening tests set forth in ASTM Specification A53/A53M (as described in section 10.3 of this Title), except that the number of tests must be at least equal to the minimum required in paragraph II-D of this Appendix to determine yield strength. .......

(II) (B) Weldability. A girth weld must be made in the pipe by a welder who is qualified under this Part. The weld must be made under the most severe conditions under which welding will be allowed in the field and by means of the same procedure that will be used in the field. On pipe more than 4 inches (102 millimeters) in diameter, at least one test weld must be made for each 100 lengths of pipe. On pipe 4 inches (102 millimeters) or less in diameter, at least one test weld must be made for each 400 lengths of pipe. The weld must be tested in accordance with API Standard 1104 (as described in section 10.3 of this Title). If the requirements of API Standard 1104 (as described in section 10.3 of this Title) cannot be met, weldability may be established by making chemical tests for carbon and manganese, and proceeding in accordance with section IX of the ASME Boiler and Pressure Vessel Code. The same number of chemical tests must be made as are required for testing girth weld.

(II) (C) Inspection. The pipe must be clean enough to permit adequate inspection. It must be visually inspected to ensure that it is reasonably round and straight and there are no defects which might impair the strength or tightness of the pipe.

(II) (D) Tensile properties. If the tensile properties of the pipe are not known, the minimum yield strength may be taken as 24,000 psi (165 MPa) or less, or the tensile properties may be established by performing tensile tests as set forth in API Specification 5L. All test specimens shall be selected at random and the following number of tests must be performed:

Number of Tensile Tests-All Sizes

10 lengths or less ....... 1 set of tests for each length.
11 to 100 lengths ....... 1 set of tests for each 5 lengths, but not less than 10 tests.
Over 100 lengths ....... 1 set of tests for each 10 lengths, but not less than 20 tests.

If the yield-tensile ratio, based on the properties determined by those tests, exceeds 0.85, the pipe may be used only as provided in section 255.55(c) of this Title.

(III) Steel pipe manufactured before November 12, 1970, to earlier editions of listed specifications. Steel pipe manufactured before November 12, 1970, in accordance with a specification of which a later edition is listed in section I of this Appendix, is qualified for use under this Part if the following requirements are met:

(III) (A) Inspection. The pipe must be clean enough to permit adequate inspection. It must be visually inspected to ensure that it is reasonably round and straight and that there are no defects which might impair the strength or tightness of the pipe.

(III) (B) Similarity of specification requirements. The edition of the listed specification under which the pipe was manufactured must have substantially the same requirements with respect to the following properties as a later edition of that specification listed in section I of this appendix:

(III) (1) Physical (mechanical) properties of pipe, including yield and tensile strength, elongation, and yield to tensile ratio, and testing requirements to verify those properties.

(III) (2) Chemical properties of pipe and testing requirements to verify those properties.

(III) (C) Inspection or test of welded pipe. On pipe with welded seams, one of the following requirements must be met:

(III) (1) The edition of the listed specification to which the pipe was manufactured must have substantially the same requirements with respect to nondestructive inspection of welded seams and the standards for acceptance or rejection and repair as a later edition of the specification listed in section I of this Appendix.

(III) (2) The pipe must be tested in accordance with this Part to at least 1.25 times the maximum allowable operating pressure if it is to be installed in a class 1 location and to at least 1.5 times the maximum allowable operating pressure if it is to be installed in a class 2, 3, or 4 location. Notwithstanding any shorter time period permitted under this Part, the test pressure must be maintained for at least 8 hours.

N.Y. Comp. Codes R. & Regs. tit. 16, Appendices, app 14-B