N.M. Admin. Code § 20.3.15.1514

Current through Register Vol. 36, No. 1, January 14, 2025
Section 20.3.15.1514 - POWER FAILURES
A. If electrical power at a panoramic irradiator is lost for longer than 10 seconds, the source must automatically return to the shielded position.
B. The lock on the door of the radiation room of a panoramic irradiator may not be deactivated by a power failure.
C. During a power failure, the area of any irradiator where sources are located may be entered only when using an operable and calibrated radiation survey meter.

N.M. Admin. Code § 20.3.15.1514

05/03/95; 20.3.15.1514 NMAC - Rn, 20 NMAC 3.1.15.1514, 4/15/2004