N.M. Code R. § 14.7.2.25

Current through Register Vol. 35, No. 16, August 27, 2024
Section 14.7.2.25 - CHAPTER 17 - SPECIAL INSPECTIONS AND TESTS

See this chapter of the IBC except as provided below.

A.Section 1705.3 - Concrete Construction. See this section of the IBC except as provided below.
(1)Subsection 2 - Delete this section of the IBC and substitute: continuous concrete footings supporting walls of buildings three stories or less in height that are fully supported on earth or rock;
(2)Subsection 3 - Delete this section of the IBC and substitute: nonstructural concrete slabs supported directly on the ground, except pre-stressed slabs-on-grade;
(3)Subsection 4 - Delete this section of the IBC with no substitution.
B.Section 1705.4 - Masonry Construction. See this section of the IBC except delete Exception 2.
C.Section 1705.18 - Fire-resistant penetrations and joints. Delete this section of the IBC and substitute with the following: In buildings three stories or greater, in buildings to Risk Category III and IV, or in fire areas containing Group R occupancies with an occupant load greater than 200, special inspections for through-penetrations, membrane penetration firestops, fire-resistant joint systems and perimeter fire containment systems that are tested and listed in accordance with Sections 714.4.1.2, 714.5.1.2, 715.3.1 and 715.4 shall be in accordance with Section 1705.18.1 or 1705.18.2.

N.M. Code R. § 14.7.2.25

14.7.2.25 NMAC - Rp, 14.7.2.25 NMAC, 1-28-11, Adopted by New Mexico Register, Volume XXVII, Issue 21, November 15, 2016, eff. 11/15/2016, Adopted by New Mexico Register, Volume XXXIV, Issue 11, June 13, 2023, eff. 7/14/2023