Current through Register Vol. 56, No. 21, November 4, 2024
Section 8:43-3A.9 - Fire extinguisher specifications(a) There shall be a minimum of two fire extinguishers in the basement, at least one on each floor of the building, and as required in kitchen areas. All fire extinguishers shall bear the seal of the Underwriters Laboratories.(b) The following types of fire extinguishers shall be provided: 1. In kitchen areas, because of danger of grease fires, extinguishers shall be of the Class B dry chemical type 2-B and a minimum of five pounds. The maximum travel distance to an extinguisher shall be 50 feet.2. In the basement area, extinguisher shall be Class B dry chemical type 2-B and a minimum of five pounds, if oil or gas is used as fuel. The maximum travel distance to an extinguisher shall be 50 feet .3. In all other areas a Class A air-pressurized 2 1/2 gallon water type 2-A extinguisher shall be provided. The maximum travel distance to an extinguisher shall be 75 feet. N.J. Admin. Code § 8:43-3A.9