Current through Register Vol. 56, No. 21, November 4, 2024
Section 8:43-15.5 - Heating and air conditioning(a) The heating and, if applicable, air conditioning system shall be adequate to maintain the required temperature in all areas used by residents. When the heating system is used, the temperature in the facility shall be kept at a minimum of 72 degrees Fahrenheit (22 degrees Celsius) during the day ("day" means the time between sunrise and sunset) and 68 degrees Fahrenheit (20 degrees Celsius) at night, when residents are in the facility. 1. Filters for heaters and air conditioners shall be provided and maintained in accordance with manufacturer's specifications.2. Tanks for all new installations of oil furnaces or other equipment shall be located outside the building. Previously installed oil storage tanks shall have the vent pipe and fill pipe located outside the building.3. An identifiable electrical emergency shut-off switch shall be provided, on the first floor, for any oil burner.4. Portable heaters shall not be permitted.(b) During warm weather conditions, the temperature of the facility shall not exceed 82 degrees Fahrenheit. 1. The facility shall establish a written heat emergency action plan which specifies procedures to be followed in the event that the indoor air temperature is 83 degrees Fahrenheit or higher for a continuous period of four hours or longer. The facility shall provide for and operate adequate ventilation in all areas used by residents. N.J. Admin. Code § 8:43-15.5