TABLE B
Relative Group Hazard
1 (highest) | H-1, H-2, H-3 |
2 | A-1, A-2 Nightclubs, H-4, H-5, F-1, I-3, M, S-1 |
3 | A-2 Other than Nightclubs, A-3, A-4, A-5, B, F-2, I-2, I-4, R-1, S-2 |
4 | A-3 Places of Worship, E, I-1, R-2, and R-4 buildings more than two stories in height or more than four dwelling units |
5 (lowest) | R-2 and R-4 buildings two stories or fewer in height and four dwelling units or less, R-3, R-5, U |
TABLE C
Hazard Categories and Classifications
Means of Egress
Relative Hazard | Use Classifications |
1 (highest) | H-1, H-2, H-3, A-2 Nightclubs |
2 | I-2, I-3, I-4 |
3 | A (other than A-2 nightclubs), E, I-1, M, R-1, R-2, R-4 |
4 | B, F-1, R-3, R-5, S-1, H-4, H-5 |
5 (lowest) | F-2, S-2, U |
TABLE E
Hazard Categories and Classifications
Height and Area
Relative Hazard | Use Classification |
1 (highest) | A-2 Nightclubs, H-1, H-2, I-2, I-3, I-4 |
2 | A-1, A-2 Other than Nightclubs, A-3, A-4, E, F-1, H-3, H-4, H-5, I-1, M, S-1 |
3 | A-3 Places of Worship, B, R-1, R-2, R-4 |
4 (lowest) | F-2, R-3, R-5, S-2, U |
TABLE F
Hazard Categories and Classifications
Exposure of Exterior Walls
Relative Hazard | Use Classification |
1 (highest) | H |
2 | Buildings exceeding 12,000 sq ft of F-1, M or S-1 |
3 | A, B, E, F-2, I, R-1, S-2 Buildings 12,000 sq ft or less of F-1, M$=B,$=R or S-1 |
4 (lowest) | R-2, R-3, R-4, R-5, U |
Requirements for Exterior Wall Fire Resistance Rating Building Use Group<b> | |||
Fire Separation Distance | H-2 | F-1, H-3, M, S-1 | A, B, E, F-2, S-2, H-4, H-5, I, R-1 |
0-5 feet | 4 | 3 | 2<a> |
Over 5-10 feet | 3 | 2 | 1 |
Over 10-15 feet | 2 | r1 | 0 |
Over 15-30 feet | r1 | -30 | 0 |
Over 30 feet | 30 | 30 | 0 |
Note a: Existing eight-inch hollow or six-inch solid masonry walls shall be accepted as a two-hour rating in other than Group H-2 or H-3. | |||
Note b: When the group of a building is changed to H-1, the building shall be located in accordance with Section 415.3 of the building subcode. |
Group | Exterior Wall Requirements |
H | No opening permitted with a fire separation distance of three feet or less. Protected openings required with a fire separation distance of 20 feet or less. |
A-1, A-2 Nightclubs, A-2 Other than Nightclubs, A-3, A-4, A-3 Places of Worship, B, E, F-1, I-1, I-2, I-3, I-4, M, S-1, R-1 | No openings permitted with a fire separation distance of three feet or less. Walls with a fire separation distance of 10 feet or less, but more than three feet, are permitted to have unprotected openings with an aggregate area not exceeding 10 percent of the area of the wall. Openings in excess of 10 percent of the aggregate wall area shall be protected. |
F-2, S-2 | No openings permitted with a fire separation distance of three feet or less. Protected openings required with a fire separation distance of five feet or less. |
TABLE G
Hazard Categories and Classifications Automatic Sprinkler Systems
Relative Hazard | Use Classification |
1 (highest) | A-2 nightclubs, H, I |
2 | A-2 (other than nightclubs), R-1, R-2, R-3, R-4 |
3 | A-1, A-3, A-4 |
4 | F-1, M, S-1 |
5 | A-3 Places of Worship, E |
6 (lowest) | A-5, B, F-2, R-5, S-2, U |
TABLE K | |
Structural Load Categories | |
Load Category | Use or Character of Use |
1 (highest) | F-1, F-2, S-1, S-2, stack areas in libraries, stages and platforms, areas subject to vehicular loads, queuing areas |
2 | All loading conditions not listed in category 1 or 3 |
3 (lowest) | B, E, I-1, I-2, I-3, I-4, R-1, R-2, R-3, R-4, R-5 |
TABLE N | ||
Outdoor Air Rates Based on Occupancy Type | ||
Occupancy | P/1,000 sq.ft. | CFM/person |
Storage Warehouses | 5 | 10 |
Correction Facilities | ||
Dining Halls | 100 | 15 |
Guard Stations | 40 | 15 |
Dry Cleaners, laundries | ||
Coin oper dry cleaner | 20 | 15 |
Coin oper laundries | 20 | 15 |
Education | ||
Auditoriums | 150 | 15 |
Classrooms | 50 | 15 |
Libraries | 20 | 15 |
Music Rooms | 50 | 15 |
Food & Bev Service | ||
Dining Rooms | 70 | 15 |
Kitchens (cooking) | 20 | 15 |
Hospitals, Nursing & | ||
Convalescent Homes | ||
Med Procedure Rooms | 20 | 15 |
Physical Therapy | 20 | 15 |
Recovery and ICU | 20 | 15 |
Hotels, Motels, Resorts, | ||
Dormitories | ||
Assembly Rooms | 120 | 15 |
Dormitory Sleep Areas | 20 | 15 |
Lobbies | 30 | 15 |
Specialty Shops | ||
Barber | 25 | 15 |
Florists | 8 | 15 |
Hardware, drug, fabric | 8 | 15 |
Reducing Salons | 20 | 15 |
Supermarkets | 8 | 15 |
Theaters | ||
Auditoriums | 150 | 15 |
Stages and Studios | 70 | 15 |
Transportation | ||
Platforms | 100 | 15 |
Vehicles | 150 | 15 |
Waiting Rooms | 100 | 15 |
Workrooms | ||
Bank Vaults | 5 | 15 |
Meat Processing | 10 | 15 |
Pharmacy | 20 | 15 |
Photo Studios | 10 | 15 |
Sports and Amusement | ||
Spectator Areas | 150 | 15 |
Correctional Facilities | ||
Cells | 20 | 20 |
Education | ||
Laboratories | 50 | 20 |
Training Shops | 30 | 20 |
Food & Bev Service | ||
Cafeteria, fast food | 100 | 20 |
Hotels, Motels, Resorts, | ||
Dormitories | ||
Conference Rooms | 50 | 20 |
Dry Cleaners | ||
Commercial Laundry | 10 | 25 |
Hospitals, Nursing and | ||
Convalescent Homes | ||
Patient Rooms | 10 | 25 |
Specialty Shops | ||
Beauty | 25 | 25 |
Dry Cleaners, Laundries | ||
Commercial Dry | ||
Cleaner | 30 | 30 |
Food & Bev Service | ||
Bars & Cocktail | ||
Lounges | 100 | 30 |
Dry Cleaners, Laundries | ||
Storage, Pick-up | 30 | 35 |
Smoking Lounges | 70 | 60 |
Offices | ||
Conference Rooms | 50 | 20 |
Office Spaces | 7 | 20 |
Reception Areas | 60 | 20 |
Telecommunication | ||
Ctrs & Data Entry | 60 | 20 |
Theaters | ||
Lobbies | 150 | 20 |
Ticket Booths | 60 | 20 |
Sports and Amusement | ||
Playing floors (gym) | 30 | 20 |
Sports and Amusement | ||
Ballrooms and Discos | 100 | 25 |
Bowling Alleys | ||
(Seating areas) | 70 | 25 |
Game Rooms | 70 | 25 |
Hospitals, Nursing & | ||
Convalescent Homes | ||
Operating Rooms | 20 | 30 |
Hotels, Motels, Resorts, | ||
Dormitories | ||
Gambling Casinos | 120 | 30 |
Occupancy | CFM/sq. ft. | |
Education | ||
Corridors | 0.1 | |
Locker Rooms | 0.5 | |
Hospitals, Nursing and | ||
Convalescent Homes | ||
Autopsy Rooms | 0.5 | |
Public Spaces | ||
Corridors and Utilities | 0.05 | |
Elevators | 1.0 | |
Locker & Dressing Rooms | 0.5 | |
Public Restrooms | 75 cfm per water closet | |
or urinal | ||
Retail Stores, Sales Floors | ||
and Showroom Floors | ||
Basement and Street | 0.3 | |
Dressing Rooms | 0.2 | |
Malls and Arcades | 0.2 | |
Shipping and Receiving | 0.15 | |
Storage Rooms | 0.15 | |
Upper Floors | 0.2 | |
Warehouses | 0.05 | |
Specialty Shops | ||
Automotive Service | 1.5 | |
Clothes and Furniture | 0.3 | |
Pet Shops | 1.0 | |
Sports & Amusement | ||
Ice Arenas | 0.5 | |
Swimming Pools | ||
(Pool & Deck Area) | 0.5 | |
Storage | ||
Repair Garages/Public | ||
Garages | 1.5 | |
Workrooms | ||
Darkrooms | 0.5 | |
Duplicating | 0.5 | |
Note: P/1,000 sq. ft. = persons per 1,000 square feet of building area. | ||
Note a. Spaces unheated or maintained below 50 degrees F are not covered | ||
by these requirements unless the occupancy is continuous. | ||
Where the ventilation rates in Table N are based on CFM/person | ||
(1) OL[n] x V[n] is less than or equal to OL[e] x V[e] | + no upgrade | |
(2) OL[n] x V[n] is greater than OL[e] x V[e] | + upgrade | |
Where the ventilation rates in Table N are based on CFM/square footage | ||
(3) SF[n]xV[n] is less than or equal to SF[e]xV[e] | + no upgrade | |
(4) SF[n]xV[n] is greater than SF[e]xV[e] | + upgrade | |
Where the ventilation rates in Table N are based on CFM/square footage | ||
and CFM/person | ||
(5) OL[n]xV[n] is less than or equal to SF[e]xV[e] | + no upgrade | |
(6) OL[n]xV[n] is greater than SF[e]xV[e] | + upgrade | |
(7) SF[n]xV[n] is less than or equal to OL[e]xV[e] | + no upgrade | |
(8) SF[n]xV[n] is greater than OL[e]xV[e] | + upgrade | |
Where: | ||
OL[n] = | the occupant load of the proposed occupancy based on | |
Table N. When accepted by the administrative authority this occupant load can be reduced. | ||
OL[e] = | the occupant load of the existing occupancy | |
based on Table N. | ||
SF[n] = | the square footage of the proposed occupancy. | |
SF[e] = | the square footage of the existing occupancy. | |
V[n] = | the ventilation rate for the proposed | |
occupancy based on Table N. | ||
V[e] = | the ventilation rate for the existing | |
occupancy based on Table N. |
N.J. Admin. Code § 5:23-6.31