N.J. Admin. Code § 5:21-5.4

Current through Register Vol. 56, No. 21, November 4, 2024
Section 5:21-5.4 - Fire hydrants
(a) Hydrants shall be spaced to provide necessary fire flow. The average building area served per hydrant shall not exceed 120,000 square feet. In addition, the distance between any dwelling and a hydrant shall not exceed 400 feet when measured along the street right-of-way.
(b) Size, type, and installation of hydrants shall conform to the following specifications, incorporated herein by reference, as appropriate:
1. Size, type, and installation of hydrants shall be in accordance with the requirements of the municipality or the water purveyor or shall conform to the AWWA Standard for Dry Barrel Fire Hydrants, ANSI/AWWA C502. Hydrants shall have at least three outlets; one outlet shall be a pumper outlet; the other outlets shall be at least two-and-one-half-inch nominal size. The pumper outlet shall face the street. All outlet nozzles shall be at least 12 inches above the adjoining grade. When a concrete slab is provided around the hydrant riser, the flange where the hydrant connects to the riser shall be at least two inches above adjacent grade. Street main connections shall not be less than six inches in diameter. Hose threads on outlets shall be compatible with existing municipal equipment and shall either conform to NFPA 1963 or shall match existing municipal requirements. A valve shall be provided on connections between hydrants and street mains. All pipe, fittings, and appurtenances supplying fire hydrants shall be AWWA or ASTM approved.
2. All fire hydrants shall conform to NFPA Standard 291.

N.J. Admin. Code § 5:21-5.4

Amended by R.1999 d.374, effective 11/1/1999 (operative May 1, 2000).
See: 31 New Jersey Register 477(a), 31 New Jersey Register 3259(a).
Rewrote (b)1.