N.J. Admin. Code § 19:4-9.26

Current through Register Vol. 56, No. 12, June 17, 2024
Section 19:4-9.26 - Enclosure openings
(a) All new construction and substantial improvements having fully enclosed areas below the lowest floor that are usable solely for parking of vehicles, building access or storage in an area other than a basement and that are subject to flooding shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a licensed professional engineer or registered architect or must meet or exceed the following minimum criteria:
1. A minimum of two openings in at least two exterior walls of each enclosed area having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding shall be provided;
2. The bottom of all openings shall be no higher than one foot above grade; and
3. Openings may be equipped with screens, louvers, or other coverings or devices provided that they permit the automatic entry and exit of flood waters.

N.J. Admin. Code § 19:4-9.26

Amended by 51 N.J.R. 1368(a), effective 8/19/2019