N.J. Admin. Code § 14:5-4.5

Current through Register Vol. 56, No. 12, June 17, 2024
Section 14:5-4.5 - Readjustment of electric meters

Each meter after being tested shall be adjusted to record within a tolerance of plus 0.3 percent and minus one percent at both light and heavy loads. These tolerances are specified to allow for necessary variations and meters must be adjusted to within the allowable tolerances as nearly as practicable to zero error. Meters removed from service are to be tested and adjusted in the meter room before being put in service again. Each electric meter shall be tested for accuracy before installation or within 30 days after being set.

N.J. Admin. Code § 14:5-4.5

Recodified from N.J.A.C. 14:5-3.5 by R.2008 d.57, effective 3/17/2008.