N.J. Admin. Code § 14:5-2.3

Current through Register Vol. 56, No. 12, June 17, 2024
Section 14:5-2.3 - Protection at crossing of cables
(a) At all crossings where buried supply conductors or cables are above communication conductors or cables, the supply conductors or cables shall be protected from digging operations by concrete or rot-resistant treated wood plank or equivalent mechanical protective covering extending at least two feet in each direction from the point of crossing.
(b) Exceptions to (a) above are as follows:
1. This separation and protection is not required where supply circuits having a potential of 550 volts or less between conductors and having a total transmitted power of not in excess of 3,200 watts are laid adjacent to communication cables, if all cables are used exclusively for the operation of a railway signal or supply system and are maintained by the same company.
2. This protection is not required where supply conductors over 550 volts between conductors are installed in accordance with 14:5-2.2(b)3 and 4.

N.J. Admin. Code § 14:5-2.3

Amended by R.1991 d.583, effective 12/2/1991.
See: 23 N.J.R. 1519(a), 23 N.J.R. 3652(a).
Editorial or stylistic change only.
Amended by R.1997 d.99, effective 3/3/1997.
See: 28 N.J.R. 4080(a), 29 N.J.R. 786(b).
Changed N.J.A.C. references.
Recodified from N.J.A.C. 14:5-1.3 and amended by R.2008 d.57, effective 3/17/2008.
See: 39 N.J.R. 3716(a), 40 N.J.R. 1684(a).
In (a), substituted "rot-resistant treated" for "creosoted"; and in (b)2, updated the N.J.A.C. reference.
Former N.J.A.C. 14:5-2.3, Sealing of main fuse cabinets and circuit breakers, recodified to N.J.A.C. 14:5-3.3.